Its interrupting capacity reaches 242 kA at 240 V, dropping to 187 kA at 415 V and 440 V, and 121 kA at 500 V — at 690 V it still holds 3.7 kA. That SCCR headroom means it can sit upstream in a high-fault panel without cascading to the main breaker, a real advantage when coordinating selectivity in a 400 V industrial distribution board.
No undervoltage release or communication module is fitted on this variant, so it is a straightforward thermal-magnetic replacement in a line-protection role.