Siemens 3VA2116-6HN32-0AJ0 SENTRON MCCB, 160 A, 3-Pole, ETU3

MPN3VA2116-6HN32-0AJ0

Siemens SENTRON 3VA2116-6HN32-0AJ0, molded case circuit breaker, 3-pole, 160 A, ETU350 electronic trip unit, 242 kA at 240 V, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2116-6HN32-0AJ0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2116-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA2116-6HN32-0AJ0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C154 A
Current at 60 °C148 A
Current at 65 °C142 A
Current at 70 °C136 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V5 kA
Power loss, max.25.5 W
3VA2116-6HN32-0AJ0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2116-6HN32-0AJ0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-6HN32-0AJ0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2116-6HN32-0AJ0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-6HN32-0AJ0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

At 415 V and 440 V it still handles 187 kA; at 500 V it drops to 121 kA; at 690 V it's rated 5 kA. For a 160 A frame, those are high-interrupt ratings, meaning this unit belongs in a high-fault location — close to a transformer or a large service entrance — where available fault current can exceed 100 kA.

Thermal derating — don't lose capacity in a hot panel

At 55 °C you derate to 154 A, at 60 °C to 148 A, at 65 °C to 142 A, and at 70 °C to 136 A.

Trip unit and auxiliary contacts

The ETU350 is an electronic trip unit — adjustable overload (Ir), short-time (Isd), and instantaneous (Ii) settings via DIP switches or rotary dials on the front face. It gives you coordination flexibility that a fixed thermal-magnetic cannot.

Three poles, line side on top, load side on bottom — straightforward bus or cable connection.

Frequently asked questions

What is the interrupting capacity of 3VA2116-6HN32-0AJ0 at 240 V?

At 240 V the interrupting capacity is 242 kA; at 415 V and 440 V it is 187 kA; at 500 V it is 121 kA; at 690 V it is 5 kA.

What trip unit does 3VA2116-6HN32-0AJ0 use?

It uses the ETU350 electronic trip unit, which provides adjustable overload, short-time, and instantaneous protection settings.

Where can I buy 3VA2116-6HN32-0AJ0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is the rated continuous current of 3VA2116-6HN32-0AJ0?

The rated continuous current Iu is 160 A, which holds steady up to 50 °C ambient before derating begins.