Skip to main content
Siemens 3VA2116-6HN32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2116-6HN32-0CA0 MCCB, 160A, 242kA at 240V

MPN3VA2116-6HN32-0CA0

Siemens SENTRON 3VA2116-6HN32-0CA0, 3-pole molded case circuit breaker, 160 A rated continuous current, ETU350 electronic trip unit, 242 kA breaking capacity at 240 V AC, undervoltage release included.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-6HN32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2116-6HN32-0AA0

Ratings

3VA2116-6HN32-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C154 A
Current at 60 °C148 A
Current at 65 °C142 A
Current at 70 °C136 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V5 kA
Power loss, max.28 W

Protection & Trip Unit

3VA2116-6HN32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350

Construction & Connection

3VA2116-6HN32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-6HN32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2116-6HN32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-6HN32-0CA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

What this MCCB is and what it does

The Siemens SENTRON 3VA2116-6HN32-0CA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection — meaning it sits on the feeder side of a distribution panel, not on a motor branch. Rated continuous current Iu is 160 A, and it holds that rating flat from 40 °C up to 50 °C; above that it derates to 154 A at 55 °C and 136 A at 70 °C. That thermal curve matters if this breaker lives in a non-climate-controlled enclosure near a heat source. Breaking capacity is the headline number here: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and still 5 kA at 690 V. That 242 kA at 240 V tells you this is built for high-fault locations — transformer secondaries or large bus risers where the available fault current is extreme. The ETU350 electronic trip unit gives you adjustable long-time, short-time, and instantaneous pickup, plus ground-fault capability if you add the right accessory. Rated insulation voltage Ui is 800 V. Maximum power loss is 28 W.

Trip unit and auxiliary release

This order code ships with the ETU350 electronic overcurrent release and an undervoltage release (UVR) as a factory-installed auxiliary release. No auxiliary contacts are included on this variant.

Physical fit and environment

Dimensions: 181 mm high, 105 mm wide, 86 mm deep. That 105 mm width is a 3-pole frame; it mounts on a DIN rail or can be screw-mounted to a backplate. Operating temperature range is -25 °C to 70 °C, storage from -40 °C to 80 °C. The 86 mm depth includes the arc chamber and terminals — make sure your enclosure depth clears that plus wiring space behind the door.

Frequently asked questions

How do I get current pricing and availability for 3VA2116-6HN32-0CA0?

Submit an RFQ with your target quantity and delivery window. We source through independent distribution and confirm current pricing and availability at quote time — no stock figures or lead-time numbers on a public listing.

Does this breaker include an undervoltage release?

Yes, the 3VA2116-6HN32-0CA0 ships with a factory-installed undervoltage release (UVR) as the auxiliary release. The UVR trips the breaker when control voltage drops below its dropout threshold, commonly used in emergency-stop or undervoltage protection circuits.

What trip unit does this MCCB use?

It uses the ETU350 electronic overcurrent release, which provides adjustable long-time, short-time, instantaneous, and ground-fault protection settings via an LCD interface on the front of the breaker.

MPN
3VA2116-6HN32-0CA0