Siemens 3VA2116-6HN32-0DL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-6HN32-0DL0 SENTRON MCCB, 160 A, 242 kA

MPN3VA2116-6HN32-0DL0

Siemens SENTRON 3VA2116-6HN32-0DL0, molded case circuit breaker, 3-pole, 160 A, 242 kA at 240 V, line protection, ETU350 release, undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-6HN32-0DL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2116-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2116-6HN32-0DL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C154 A
Current at 60 °C148 A
Current at 65 °C142 A
Current at 70 °C136 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V5 kA
Power loss, max.28 W

Protection & Trip Unit

3VA2116-6HN32-0DL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350

Construction & Connection

3VA2116-6HN32-0DL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-6HN32-0DL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2116-6HN32-0DL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-6HN32-0DL0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

What this MCCB delivers on the line

The Siemens SENTRON 3VA2116-6HN32-0DL0 is a 3-pole molded case circuit breaker rated for 160 A continuous current (Iu) with a line protection profile — meaning it's tuned for feeder and main distribution duty, not motor branch protection. The ETU350 electronic trip unit gives you adjustable overload and short-circuit curves, plus an integrated undervoltage release (UVR) that drops the breaker when control voltage falls below the dropout threshold. Breaking capacity is the headline here: 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and still 5 kA at 690 V. That's a serious SCCR rating — it can interrupt fault currents up to 242 kA without welding or cascading failure upstream. For a 160 A frame, that's high-end interrupting capability, suited for high-fault utility feeds or transformer secondaries. Thermal derating is published: full 160 A from 40 °C through 50 °C, then steps down to 154 A at 55 °C, 148 A at 60 °C, 142 A at 65 °C, and 136 A at 70 °C. If your panel ambient runs above 50 °C, size the breaker for the derated value — not the nameplate 160 A.

Panel fit and mounting

Footprint is 105 mm wide, 181 mm tall, 86 mm deep — standard SENTRON 3VA2 fixed-mount dimensions. Bolts directly to a backplate or mounts on a DIN rail via the optional adapter. The 86 mm depth leaves clearance for gland plates and rear cable entry; watch the bend radius on 160 A cable lugs. Auxiliary contact block is populated: 2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ. That covers remote status feedback and alarm annunciation without adding a separate module. The undervoltage release (UVR) is built in, so you don't need to order it separately — it's part of the -0DL0 suffix.

Frequently asked questions

What is the breaking capacity of this MCCB?

242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V.

What trip unit does the 3VA2116-6HN32-0DL0 use?

It uses the ETU350 electronic trip unit, adjustable for line protection applications.

Does this breaker include an undervoltage release?

Yes, an undervoltage release (UVR) is integrated as part of the order code suffix.

Where can I buy 3VA2116-6HN32-0DL0?

Sourced to order against an RFQ through independent distribution. Submit a request for current pricing and lead time.

MPN
3VA2116-6HN32-0DL0