Breaking capacity is the headline here: 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and still 5 kA at 690 V. Thermal derating is published: full 160 A from 40 °C through 50 °C, then steps down to 154 A at 55 °C, 148 A at 60 °C, 142 A at 65 °C, and 136 A at 70 °C.
That covers remote status feedback and alarm annunciation without adding a separate module.