Skip to main content
Siemens 3VA2116-6HN32-0DL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-6HN32-0DL0 SENTRON MCCB, 160 A, 242 kA

MPN3VA2116-6HN32-0DL0

Siemens SENTRON 3VA2116-6HN32-0DL0, molded case circuit breaker, 3-pole, 160 A, 242 kA at 240 V, line protection, ETU350 release, undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2116-6HN32-0DL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2116-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2116-6HN32-0DL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C154 A
Current at 60 °C148 A
Current at 65 °C142 A
Current at 70 °C136 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V5 kA
Power loss, max.28 W
3VA2116-6HN32-0DL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2116-6HN32-0DL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-6HN32-0DL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2116-6HN32-0DL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-6HN32-0DL0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Breaking capacity is the headline here: 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and still 5 kA at 690 V. Thermal derating is published: full 160 A from 40 °C through 50 °C, then steps down to 154 A at 55 °C, 148 A at 60 °C, 142 A at 65 °C, and 136 A at 70 °C.

That covers remote status feedback and alarm annunciation without adding a separate module.

Frequently asked questions

What is the breaking capacity of this MCCB?

242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V.

What trip unit does the 3VA2116-6HN32-0DL0 use?

It uses the ETU350 electronic trip unit, adjustable for line protection applications.

Does this breaker include an undervoltage release?

Yes, an undervoltage release (UVR) is integrated as part of the order code suffix.

Where can I buy 3VA2116-6HN32-0DL0?

Sourced to order against an RFQ through independent distribution. Submit a request for current pricing and lead time.

MPN
3VA2116-6HN32-0DL0