Skip to main content
Siemens 3VA2116-6HN32-0KC0 — Molded Case Circuit Breakers (MCCB)

3VA2116-6HN32-0KC0 SENTRON MCCB, 160 A, 3-pole, 242 kA at 24

MPN3VA2116-6HN32-0KC0

Siemens SENTRON 3VA2116-6HN32-0KC0, molded case circuit breaker, 3-pole, 160 A, 242 kA at 240 V, line protection, with shunt trip and 2 auxiliary switches HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-6HN32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21166HN320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2116-6HN32-0KC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.25.5 W

Protection & Trip Unit

3VA2116-6HN32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2116-6HN32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-6HN32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2116-6HN32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-6HN32-0KC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

160 A MCCB for line protection — what the ratings mean

The Siemens SENTRON 3VA2116-6HN32-0KC0 is a 3-pole molded case circuit breaker rated 160 A continuous at 40 °C through 70 °C — no derating needed across that span, which simplifies panel thermal budgeting. Breaking capacity hits 242 kA at 240 V, stepping down to 187 kA at 415/440 V, 121 kA at 500 V, and 3.7 kA at 690 V. That 242 kA figure at 240 V means it safely interrupts faults up to that level without cascading upstream — critical for high-fault service-entrance or sub-distribution boards where available short-circuit current is high. The shunt trip (STL) release allows remote tripping via a control signal, and the two HQ auxiliary switches provide status feedback to a PLC or annunciator.

Panel integration and dimensions

Dimensions are 105 mm wide, 181 mm tall, 86 mm deep. The 105 mm width is a standard 3-pole MCCB footprint for DIN-rail or panel-mount installation. The shunt trip and auxiliary switches are factory-installed — no field-assembly of those accessories. Line protection design means the breaker is configured for feeder or main protection, not motor-circuit protection (no overload relay curve).

Frequently asked questions

What is the continuous current rating of this MCCB?

Rated 160 A continuous from 40 °C to 70 °C ambient — no derating required across that range.

What breaking capacity does it have at 240 V?

242 kA at 240 V, which covers high-fault service-entrance applications.

Where can I buy 3VA2116-6HN32-0KC0?

Sourced and quoted to order against an RFQ through independent distribution — availability and current pricing confirmed at quote time.

MPN
3VA2116-6HN32-0KC0