Skip to main content
Siemens 3VA2116-6HN32-0KL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-6HN32-0KL0 SENTRON MCCB, 160 A, 3-Pole, 242

MPN3VA2116-6HN32-0KL0

Siemens SENTRON 3VA2116-6HN32-0KL0, molded case circuit breaker, 3-pole, 160 A continuous, interrupting 242 kA at 240 V, 187 kA at 415 V, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-6HN32-0KL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21166HN320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2116-6HN32-0KL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.25.5 W

Protection & Trip Unit

3VA2116-6HN32-0KL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2116-6HN32-0KL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-6HN32-0KL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2116-6HN32-0KL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-6HN32-0KL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What the ratings mean for fit

The Siemens 3VA2116-6HN32-0KL0 is a SENTRON molded case circuit breaker rated for 160 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed as the panel warms up. Its 242 kA interrupting capacity at 240 V and 187 kA at 415 V mean it can clear high-fault currents on large transformers or busway feeds without cascading upstream. At 690 V the interrupting drops to 3.7 kA, so verify the available fault current if this lands on a 690 V system. The 3-pole design and line-protection profile suit it for main incoming or feeder duty in a distribution panel. Power loss is 25.5 W maximum, which matters for enclosure thermal calculations — a sealed stainless cabinet with this breaker at full load needs ventilation or a larger volume to stay below the 70 °C operating limit.

Integration and accessories

Dimensions are 86 mm deep, 105 mm wide, 181 mm high — fits standard MCCB panel cutouts and DIN-rail adapters. The basic switch supplied is 3VA21166HN320AA0. Auxiliary switch configuration includes 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch HQ. A shunt trip (STL) release is built in for remote tripping. No undervoltage release or ground-fault monitoring on this variant.

Frequently asked questions

What are the key interrupting ratings for 3VA2116-6HN32-0KL0?

242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V.

Where can I buy 3VA2116-6HN32-0KL0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the continuous current rating of this MCCB?

160 A continuous, with no derating required from 40 °C through 70 °C ambient.

Does 3VA2116-6HN32-0KL0 include a shunt trip?

Yes, it includes a shunt trip (STL) release for remote tripping. No undervoltage release or ground-fault monitoring on this variant.

MPN
3VA2116-6HN32-0KL0