Siemens 3VA2116-6HN36-0LC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-6HN36-0LC0 Circuit Breaker, 160 A, 85 kA @ 4

MPN3VA2116-6HN36-0LC0

Siemens 3VA2 IEC Frame 160, switching capacity class H, Icu=85 kA @ 415 V, 3-pole, system protection ETU350 LSI, In=160 A, overload Ir=63…160 A, short-circuit Isd=1.5…10 x Ir, Ii=10 x In, terminal connection, universal release 24 V DC, 2 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

Siemens 3VA2116-6HN36-0LC0 is a 3-pole IEC Frame 160 molded-case circuit breaker with switching capacity class H — Icu rated 85 kA at 415 V. It carries the ETU350 LSI trip unit, adjustable overload protection Ir from 63 A to 160 A, short-circuit pickup Isd from 1.5 to 10 x Ir, and instantaneous Ii fixed at 10 x In. The universal release operates on 24 V DC, and the breaker ships with two HQ auxiliary switches.

Frame 160 mounts into standard panel cutouts and accepts lug or terminal-connection kits. The ETU350 LSI trip unit is field-adjustable — Ir, Isd, and Ii settings let the commissioning engineer match the breaker to the downstream cable and load without swapping the trip unit. The 24 V DC universal release allows remote shunt-trip integration into a safety circuit or PLC-controlled emergency-stop chain.

Frequently asked questions

Where can I buy 3VA2116-6HN36-0LC0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What is the interrupting rating of 3VA2116-6HN36-0LC0?

Icu is 85 kA at 415 V AC — switching capacity class H, suitable for high-fault utility connections or large transformer secondaries.

What trip unit does 3VA2116-6HN36-0LC0 use?

It uses the ETU350 LSI electronic trip unit with adjustable overload (Ir=63…160 A), short-time pickup (Isd=1.5…10 x Ir), and fixed instantaneous (Ii=10 x In).

MPN
3VA2116-6HN36-0LC0