Siemens 3VA2116-6JP36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-6JP36-0AA0 SENTRON MCCB, 160 A, 242 kA at 24

MPN3VA2116-6JP36-0AA0
Active

Siemens SENTRON 3VA2116-6JP36-0AA0, molded case circuit breaker, 3-pole, 160 A, ETU550 electronic release, breaking capacity 242 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-6JP36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2116-6JP36-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.8 kA
Power loss, max.25.5 W

Protection & Trip Unit

3VA2116-6JP36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550

Construction & Connection

3VA2116-6JP36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-6JP36-0AA0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2116-6JP36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-6JP36-0AA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.1 in
Width (in)4.1 in
Depth (in)3.4 in

Product details

MCCB for high-fault panels

The Siemens SENTRON 3VA2116-6JP36-0AA0 is a 3-pole molded case circuit breaker rated for a continuous current of 160 A across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. The ETU550 electronic trip unit gives you adjustable long-time (tr) from 0.5 to 20 s and short-time (tsd) up to 0.5 s, so you can shape the curve for selective coordination downstream. Breaking capacity sits at 242 kA at 240 V and 187 kA at 415 V — that's SCCR headroom for high-fault industrial panels where a main breaker must clear a bolted fault without upstream devices seeing it. At 690 V the rating drops to 3.8 kA, which is still adequate for most 690 V motor circuits in IEC territory.

Integration and mounting

Dimensions are 105 mm wide, 181 mm tall, and 86 mm deep — fits a standard MCCB footprint on a DIN rail or panel-mount plate. The IP40 front protection means it's suited for enclosed panels where the door provides the environmental seal. Rated insulation voltage is 800 V, which covers 480/277 V and 600 V systems with margin. Maximum power loss is 25.5 W — relevant for thermal calculations in a densely populated enclosure. Latching endurance is rated at 20 000 operations, so it's not a daily-switching device; it's a distribution breaker for infrequent manual operation or fault clearing.

Frequently asked questions

Where can I buy 3VA2116-6JP36-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2116-6JP36-0AA0 at 415 V?

The breaking capacity is 187 kA at 415 V, which provides substantial fault-clearing headroom for industrial main feeders.

What trip unit does 3VA2116-6JP36-0AA0 use?

It uses the ETU550 electronic trip unit with adjustable long-time delay (tr) from 0.5 to 20 s and short-time delay (tsd) up to 0.5 s, allowing selective coordination with downstream breakers.

MPN
3VA2116-6JP36-0AA0