Skip to main content
Siemens 3VA2116-7HL36-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-7HL36-0AH0 SENTRON MCCB, 160 A, 3-Pole, 330

MPN3VA2116-7HL36-0AH0

Siemens SENTRON 3VA2116-7HL36-0AH0, molded case circuit breaker, 3-pole, 160 A, ETU320 electronic trip unit, 330 kA interrupting capacity at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-7HL36-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21167HL360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2116-7HL36-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.25.5 W

Protection & Trip Unit

3VA2116-7HL36-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2116-7HL36-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-7HL36-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2116-7HL36-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-7HL36-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens 3VA2116-7HL36-0AH0 — 160 A SENTRON MCCB with ETU320 Trip Unit

The Siemens 3VA2116-7HL36-0AH0 is a 3-pole SENTRON molded case circuit breaker rated for 160 A continuous current at 40 °C, with the same rating holding flat through 70 °C — no derating needed across the full operating temperature range. The interrupting capacity reaches 330 kA at 240 V AC, 242 kA at 415 V, and 187 kA at 500 V, dropping to 3.7 kA at 690 V. This is a high-interrupting MCCB sized for main or feeder protection in distribution panels where fault current levels are substantial. The electronic trip unit is an ETU320, a fixed-setting, non-communicating release with thermal-magnetic-like curves but better selectivity coordination than a thermal-magnetic breaker. The front face carries IP40 protection, suitable for enclosed panel mounting where the breaker is behind a closed door.

What the Ratings Mean for Your Panel

The 160 A rating is continuous at 40 °C ambient, and critically, it does not derate at 45, 50, 55, 60, 65, or 70 °C — the full 160 A is available all the way to the maximum operating temperature of 70 °C. That simplifies thermal calculations in a crowded enclosure. The 800 V rated insulation voltage (Ui) means the breaker is suitable for 690 V line-to-line systems with margin. The 330 kA interrupting rating at 240 V tells you this breaker can clear very high fault currents at lower voltages — typical for a main breaker position on a large transformer secondary. At 690 V the rating drops to 3.7 kA, which is still adequate for most 690 V motor circuits but not for high-fault buswork. The ETU320 release provides adjustable overload and short-circuit protection bands, though the exact settings are fixed at the factory per the order code variant. Power loss is 25.5 W maximum at rated current — a figure to include in enclosure thermal calculations, especially if multiple breakers are ganged in a single panel.

Integration and Mounting

The breaker occupies 105 mm width × 181 mm height × 86 mm depth — a standard 3-pole MCCB footprint for 160 A frame size. It mounts on a DIN rail or directly to a backplate via the integrated mounting points. The auxiliary switch configuration is 2 auxiliary switches plus 1 trip alarm switch (HQ), factory-installed, which provides status feedback for the open/closed and tripped conditions without additional wiring.

Frequently asked questions

How do I get current pricing and availability for 3VA2116-7HL36-0AH0?

Submit an RFQ through the storefront. Pricing and stock are confirmed at quote time through independent distribution; no online price or count is displayed.

What is the interrupting capacity of this MCCB at 240 V?

330 kA at 240 V AC. At 415 V and 440 V it is 242 kA, at 500 V it is 187 kA, and at 690 V it is 3.7 kA.

What trip unit does the 3VA2116-7HL36-0AH0 use?

It uses the ETU320 electronic trip unit, a fixed-setting release with no communication function and no undervoltage release.

MPN