Skip to main content
Siemens 3VA2116-8HL46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-8HL46-0AA0 SENTRON MCCB, 160 A, 4-Pole, ETU3

MPN3VA2116-8HL46-0AA0
Active

Siemens SENTRON 3VA2116-8HL46-0AA0, molded case circuit breaker, 4-pole, 160 A, ETU320 electronic trip unit, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2116-8HL46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2116-8HL46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V53 kA
Power loss, max.19.7 W
3VA2116-8HL46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2116-8HL46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-8HL46-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2116-8HL46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-8HL46-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

160 A MCCB with ETU320 — current production, panel-ready

Four poles, line protection version, fitted with the ETU320 electronic trip unit. The 440 kA interrupting rating at 240 V (330 kA at 415 V, 220 kA at 500 V, 53 kA at 690 V) gives substantial SCCR headroom for most industrial distribution panels without needing a current-limiting upstream device.

The ETU320 release is an electronic trip unit with adjustable long-time pickup and delay (tr adjustable from 0.5 s to 17 s). Neutral protection configurable: OFF, 50%, or 100% of phase rating. No ground-fault monitoring on this version — if that's needed, you'd step to a variant with the G option.

Frequently asked questions

What is the interrupting rating of 3VA2116-8HL46-0AA0 at 240 V?

440 kA at 240 V, with 330 kA at 415/440 V, 220 kA at 500 V, and 53 kA at 690 V.

Where can I buy 3VA2116-8HL46-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

MPN
3VA2116-8HL46-0AA0