Skip to main content
Siemens 3VA2116-8JP36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-8JP36-0AA0 SENTRON MCCB, 160 A, 440 kA at 24

MPN3VA2116-8JP36-0AA0
Active

Siemens SENTRON 3VA2116-8JP36-0AA0, molded case circuit breaker, 3-pole, 160 A, ETU550 electronic trip unit, 440 kA at 240 V, communication-capable.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-8JP36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2116-8JP36-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V53 kA
Power loss, max.25.5 W

Protection & Trip Unit

3VA2116-8JP36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI

Construction & Connection

3VA2116-8JP36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-8JP36-0AA0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2116-8JP36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-8JP36-0AA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.1 in
Width (in)4.1 in
Depth (in)3.4 in

Product details

The Siemens SENTRON 3VA2116-8JP36-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 160 A continuous current, with an ETU550 electronic trip unit. Its headline interrupting rating hits 440 kA at 240 V, dropping to 330 kA at 415 V and 440 V, 220 kA at 500 V, and 53 kA at 690 V — that SCCR headroom covers most industrial distribution panels feeding motor control centers or welding lines without needing upstream current-limiting fuses.

What the ratings mean for fit

The 160 A rating holds flat across the full ambient range from 40 °C to 70 °C — no derating curve to chase when the panel sits near a furnace line or a hot transformer bay. That thermal stability matters for a body-shop weld line where ambient can spike mid-shift and you can't afford a nuisance trip at takt time. The ETU550 electronic trip unit gives adjustable long-time pickup (Ir) and short-time delay (tsd from 0.05 s to 0.5 s), plus an adjustable instantaneous pickup. That means you can coordinate selectively downstream with feeder breakers — critical on a multi-drop power distribution bus where a fault on one branch shouldn't drop the whole panel. With communication function onboard, this MCCB can report trip events and load current over a fieldbus network — no separate current transformer or I/O module needed. That saves a DIN rail slot and simplifies the BOM for a controls integrator wiring a safety CPU separation.

Lifecycle and sourcing reality

The lifecycle stage is marked as current — meaning Siemens still actively manufactures and supports this order code. No last-time-buy notice or phase-out date is available.

Integration and mounting

Dimensions are 181 mm high, 105 mm wide, 86 mm deep — fits standard MCCB panel cutouts and busbar centers. The front face carries IP40 protection, adequate for enclosed switchgear but not for washdown zones. Mounting is via screw-clamp terminals to busbars or cable lugs; no DIN-rail adapter on this frame size.

MPN
3VA2116-8JP36-0AA0