The breaking capacity at 240 V AC is 440 kA, dropping to 330 kA at 415 V and 440 V, 220 kA at 500 V, and 53 kA at 690 V. That 440 kA figure at 240 V covers high-fault utility feeds; the 53 kA at 690 V still clears most industrial fault levels. The ETU860 electronic trip unit provides adjustable long-time delay (tr) from 0.5 s to 20 s, plus ground-fault summation on L+N. Communication function is built in — no separate module needed for remote monitoring. Front IP40 protects against tool entry in the panel.

Siemens 3VA2116-8KQ46-0AA0 SENTRON MCCB, 160 A, 4-pole, 440
MPN3VA2116-8KQ46-0AA0
Active
Siemens SENTRON 3VA2116-8KQ46-0AA0, molded case circuit breaker, line protection, 4-pole, 160 A rated continuous current, breaking capacity 440 kA at 240 V AC, 330 kA at 415 V AC, 330 kA at 440 V AC, 220 kA at 500 V AC, 53 kA at 690 V AC.
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Product version | Line protection |
| Parameter | Value |
|---|---|
| Number of poles | 4 |
| Current at 40 °C | 160 A |
| Current at 45 °C | 160 A |
| Current at 50 °C | 160 A |
| Current at 55 °C | 160 A |
| Current at 60 °C | 160 A |
| Current at 65 °C | 160 A |
| Current at 70 °C | 160 A |
| Switching capacity class | L |
| Breaking capacity at 240 V | 440 kA |
| Breaking capacity at 415 V | 330 kA |
| Breaking capacity at 440 V | 330 kA |
| Breaking capacity at 500 V | 220 kA |
| Breaking capacity at 690 V | 53 kA |
| Power loss, max. | 19.7 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU860 |
| Parameter | Value |
|---|---|
| Main circuit connection type | box terminal |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Communication function | Yes |
| Measurement function | Yes |
| Motor drive option | Yes |
| Auxiliary CO contacts | 0 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -40 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Height | 181 mm |
| Width | 140 mm |
| Depth | 86 mm |
| Height (in) | 7.1 in |
| Width (in) | 5.5 in |
| Depth (in) | 3.4 in |
Product details
Frequently asked questions
What is the breaking capacity of 3VA2116-8KQ46-0AA0 at 240 V?
440 kA at 240 V AC; also 330 kA at 415 V and 440 V, 220 kA at 500 V, and 53 kA at 690 V.
Where can I buy 3VA2116-8KQ46-0AA0?
Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.
MPN