Skip to main content
Siemens 3VA2125-6HK36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2125-6HK36-0AA0 SENTRON MCCB, 25 A, 242 kA at 240

MPN3VA2125-6HK36-0AA0
Active

Siemens SENTRON 3VA2125-6HK36-0AA0, 3-pole molded case circuit breaker, 25 A rated current, ETU340 release, 242 kA at 240 V, 86 mm depth × 105 mm width × 181 mm height.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2125-6HK36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2125-6HK36-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V42 kA
Power loss, max.0.6 W

Protection & Trip Unit

3VA2125-6HK36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340

Construction & Connection

3VA2125-6HK36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2125-6HK36-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2125-6HK36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2125-6HK36-0AA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.1 in
Width (in)4.1 in
Depth (in)3.4 in

Product details

What this MCCB delivers

The Siemens 3VA2125-6HK36-0AA0 is a SENTRON molded case circuit breaker (MCCB) carrying a rated continuous current Iu of 25 A across its full operating temperature range from -40 °C to 70 °C — no derating needed up to 70 °C ambient. Three poles, line-protection version, fitted with the ETU340 electronic overcurrent release. The 242 kA breaking capacity at 240 V (187 kA at 415 V, 121 kA at 500 V, 42 kA at 690 V) gives serious fault-interruption headroom for high-available-fault-current installations.

Breaking capacity — what the numbers mean for coordination

The 242 kA at 240 V is the ultimate short-circuit breaking capacity (Icu) for this 3VA2125 frame. That figure drops to 187 kA at 415/440 V and 121 kA at 500 V, still well above typical panel SCCR requirements. At 690 V the 42 kA rating still clears most industrial fault levels. The ETU340 release is adjustable for long-time pickup and short-time delay, letting you coordinate downstream feeders without sacrificing selectivity.

Panel fit and mounting

Dimensions: 86 mm depth, 105 mm width, 181 mm height. The 3VA2 frame mounts on a DIN rail or can be screw-fixed to a backplate. Front IP40 protection keeps dust and accidental contact out of the breaker face. Optional motor drive available for remote tripping or reset.

Frequently asked questions

What is the breaking capacity of 3VA2125-6HK36-0AA0 at 240 V?

242 kA at 240 V, with 187 kA at 415/440 V, 121 kA at 500 V, and 42 kA at 690 V.

What overcurrent release does this MCCB use?

The ETU340 electronic release, adjustable for long-time pickup and short-time delay.

Where can I buy 3VA2125-6HK36-0AA0 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA2125-6HK36-0AA0