Skip to main content
Siemens 3VA2125-6HL32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2125-6HL32-0AA0 SENTRON MCCB, 25 A, 242 kA at 240

MPN3VA2125-6HL32-0AA0
Active

Siemens SENTRON 3VA2125-6HL32-0AA0, 3-pole molded case circuit breaker, 25 A rated continuous current, ETU320 electronic trip unit, 242 kA breaking capacity at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2125-6HL32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2125-6HL32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.0.6 W

Protection & Trip Unit

3VA2125-6HL32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2125-6HL32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2125-6HL32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2125-6HL32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2125-6HL32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB delivers — and where the ratings matter

The Siemens SENTRON 3VA2125-6HL32-0AA0 is a 3-pole molded case circuit breaker rated for 25 A continuous current, with an ETU320 electronic trip unit designed for line protection. The headline number here is the breaking capacity: 242 kA at 240 V AC, dropping to 187 kA at 415 V and 440 V, then 121 kA at 500 V, and 3.7 kA at 690 V. That means this breaker can safely interrupt fault currents up to those levels without welding contacts or cascading failure upstream — critical for high-fault panels near large transformers or motor control centers. The 25 A rating holds flat across the full ambient range from 40 °C to 70 °C, so no derating curve to calculate in a warm enclosure. Insulation voltage is rated 800 V, giving headroom for 480 V and 600 V class systems.

Panel fit and integration

Dimensions are 105 mm wide, 181 mm tall, and 86 mm deep — a standard SENTRON 3VA frame size that fits existing Siemens MCCB mounting bases and busbar systems. The front face carries IP40 protection, meaning it's sealed against tools and wires but not washdown; suitable for indoor panel mounting. Operating range spans -25 °C to 70 °C, storage from -40 °C to 80 °C. No undervoltage release, no communication module, no ground-fault monitoring on this variant — it's a straight line-protection breaker with the ETU320 trip unit handling overload and short-circuit curves.

Frequently asked questions

What is the breaking capacity of 3VA2125-6HL32-0AA0 at different voltages?

242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V. These are the maximum fault currents the breaker can safely interrupt at each voltage level.

Where can I buy 3VA2125-6HL32-0AA0 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit a request and we'll provide a firm commercial offer.

What trip unit does this MCCB use?

It uses the ETU320 electronic overcurrent release, designed for line protection. This is the current-generation electronic trip unit for the 3VA2 platform.

MPN
3VA2125-6HL32-0AA0