Skip to main content
Siemens 3VA2125-6HL42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2125-6HL42-0AA0 SENTRON MCCB, 25 A, 4-Pole, 242 k

MPN3VA2125-6HL42-0AA0
Active

Siemens SENTRON 3VA2125-6HL42-0AA0, molded case circuit breaker, 4-pole, 25 A, line protection, ETU320 release, breaking capacity 242 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2125-6HL42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2125-6HL42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.8 kA
Power loss, max.0.6 W

Protection & Trip Unit

3VA2125-6HL42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320

Construction & Connection

3VA2125-6HL42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2125-6HL42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2125-6HL42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2125-6HL42-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

What this MCCB is and what it does

The Siemens 3VA2125-6HL42-0AA0 is a SENTRON molded case circuit breaker (MCCB) configured for line protection — meaning it guards feeders and distribution branches against overcurrent and short-circuit faults, not motor loads. It carries a rated continuous current Iu of 25 A across its full ambient temperature range from 40 °C to 70 °C with no derating, which simplifies panel sizing in warm enclosures. The 4-pole design switches all three phases plus neutral, with the N-conductor protection adjustable to OFF or 100% of the phase rating. The ETU320 electronic trip unit gives you adjustable time-current curves — the long-time delay tr is settable between 0.5 and 17 seconds — so you can coordinate selectivity downstream without oversizing the main breaker. Rated insulation voltage Ui is 800 V, and the front face carries IP40 protection, adequate for dry indoor panel installations.

Breaking capacity — what the numbers mean for your fault duty

This MCCB delivers 242 kA at 240 V, 187 kA at 415 V and at 440 V, 121 kA at 500 V, and 3.8 kA at 690 V. Those are the ultimate short-circuit breaking capacities (Icu) at each voltage level — the fault current the breaker can safely interrupt once. At 415 V, 187 kA covers nearly any industrial transformer secondary or high-fault panel bus; the drop to 3.8 kA at 690 V means it's not intended for 690 V main feeders, but for 400/415 V distribution it has headroom to spare.

Panel fit and dimensions

The breaker measures 140 mm wide, 181 mm high, and 86 mm deep — a standard SENTRON 3VA2 frame footprint that drops into existing panel cutouts and busbar systems designed for the series. The 4-pole width (140 mm) is wider than a 3-pole unit; verify your busbar spacing and enclosure depth before committing the BOM. An optional motor drive can be added as a product extension for remote tripping or re-closing schemes.

Frequently asked questions

Where can I buy 3VA2125-6HL42-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote — availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2125-6HL42-0AA0 at 415 V?

It is rated 187 kA at 415 V, which covers most industrial transformer secondary faults.

Does the 3VA2125-6HL42-0AA0 require derating at elevated ambient temperatures?

No — the rated continuous current of 25 A holds from 40 °C through 70 °C with no derating step.

MPN
3VA2125-6HL42-0AA0