Skip to main content
Siemens 3VA2125-7HK46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2125-7HK46-0AA0 MCCB, 25 A, 4-Pole, 330 k

MPN3VA2125-7HK46-0AA0
Active

Siemens SENTRON 3VA2125-7HK46-0AA0, Molded case circuit breaker, Line protection, 4-pole, 25 A, 330 kA at 240 V, ETU340 release, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2125-7HK46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2125-7HK46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V53 kA
Power loss, max.0.6 W

Protection & Trip Unit

3VA2125-7HK46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340

Construction & Connection

3VA2125-7HK46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2125-7HK46-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2125-7HK46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2125-7HK46-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

The Siemens SENTRON 3VA2125-7HK46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 25 A continuous current across the full operating temperature range of -40 °C to 70 °C — no derating needed from 40 °C through 70 °C, which simplifies panel sizing in hot environments like switchgear rooms or outdoor enclosures. Breaking capacity hits 330 kA at 240 V, 242 kA at 415/440 V, 187 kA at 500 V, and 53 kA at 690 V — numbers that place this squarely in high-fault-duty applications like industrial main feeders or transformer secondaries where upstream SCCR demands serious headroom. Fitted with an ETU340 electronic trip unit, adjustable N-conductor protection (OFF or 100%), and a fixed long-time delay of 1300 s at tr max/min — a line-protection MCCB, not a motor-protection device, so it's sized for cable and busbar protection in distribution panels.

What the ratings mean for fit

The 800 V rated insulation voltage (Ui) confirms this MCCB is rated for 690 V systems with margin — common in 480/277 V and 600 V North American panels, and standard for 400/690 V European industrial grids. IP40 on the front means it's protected against tools and solid objects larger than 1 mm, but not sealed against moisture — install in a dry enclosure or a panel with a higher-rated door. Mechanical endurance of 20,000 cycles (latching) suits fixed installations where the breaker sees infrequent switching — not a daily disconnect switch for motor starting. Maximum power loss of 0.6 W per pole is negligible for thermal management in densely packed panels — no forced cooling needed around this unit.

Lifecycle and sourcing reality

Sourced and quoted to order against an RFQ through independent distribution — availability and current pricing confirmed at quote time. No official successor order code exists; the 3VA2 platform is the current generation for this class. Panel footprints are consistent across the 3VA2 family, so a 25 A frame shares the same mounting pattern as other ratings in the series.

Panel integration

Dimensions: 181 mm height, 140 mm width, 86 mm depth — fits standard MCCB mounting footprints in Siemens SENTRON distribution boards or generic DIN-rail enclosures with screw-fixed backplates. No communication function onboard — this is a standalone thermal-magnetic (electronic trip) breaker with no Modbus or PROFIBUS interface. For remote monitoring, pair with an external power metering module or a separate communication-capable feeder.

Frequently asked questions

Where can I buy 3VA2125-7HK46-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 3VA2125-7HK46-0AA0 at 415 V?

242 kA at 415 V and 440 V, 187 kA at 500 V, and 53 kA at 690 V.

What trip unit does 3VA2125-7HK46-0AA0 use?

An ETU340 electronic overcurrent release with adjustable N-conductor protection (OFF or 100%) and a fixed long-time delay of 1300 s.

MPN
3VA2125-7HK46-0AA0