Skip to main content
Siemens 3VA2125-7HL32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2125-7HL32-0AA0 SENTRON MCCB, 25A, 330kA at 240V

MPN3VA2125-7HL32-0AA0
Active

Siemens SENTRON 3VA2125-7HL32-0AA0, 3-pole molded case circuit breaker, 25 A rated current, 330 kA breaking capacity at 240 V AC, ETU320 electronic trip unit, line protection version.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2125-7HL32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2125-7HL32-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.8 kA
Power loss, max.0.6 W

Protection & Trip Unit

3VA2125-7HL32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VA2125-7HL32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2125-7HL32-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2125-7HL32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2125-7HL32-0AA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.1 in
Width (in)4.1 in
Depth (in)3.4 in

Product details

What this MCCB delivers on the line

The Siemens 3VA2125-7HL32-0AA0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated for 25 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed as the panel warms up. Its ETU320 electronic trip unit gives you adjustable short-circuit pickup (Iᵢ) from 38 A to 300 A, so you tune the magnetic trip to the inrush of a motor or the fault tolerance of a feeder without swapping the breaker. Breaking capacity hits 330 kA at 240 V AC, dropping to 242 kA at 415 V and 440 V, then 187 kA at 500 V, and 3.8 kA at 690 V. That 330 kA figure means it handles the full let-through of a large transformer or a utility-grade fault on a 240 V distribution bus — not a rating you see on a 25 A frame every day.

Panel fit and integration

Dimensions come in at 105 mm wide, 181 mm tall, and 86 mm deep — a standard SENTRON 3VA2 frame footprint. IP40 on the front face keeps dust out of the trip-unit compartment in a closed panel. The line-protection version (no ground-fault monitoring) saves space on the DIN rail or mounting plate when you only need overcurrent and short-circuit protection. Optional motor drive is available as a field-fit accessory, so the breaker can be remotely racked or reset without opening the door. Communication function is not built in — this is a standalone thermal-magnetic replacement, not a smart breaker with Modbus or PROFINET on board.

Frequently asked questions

Where can I buy 3VA2125-7HL32-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 3VA2125-7HL32-0AA0 at 240 V?

The breaking capacity is 330 kA at 240 V AC, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.8 kA at 690 V.

Does this breaker have a communication function or ground-fault monitoring?

No. Communication function is not included, and this version ships without ground-fault monitoring. It is a line-protection MCCB with the ETU320 electronic trip unit.

MPN
3VA2125-7HL32-0AA0