Its breaking capacity reaches 330 kA at 240 V AC and 242 kA at 415 V AC, dropping to 3.7 kA at 690 V AC — the voltage-dependent curve means you size the interrupting rating against the actual fault level at the installation point, not the highest number on the label. Power loss is 0.6 W maximum, negligible for panel thermal budget.
Depth of 86 mm is the body only; allow additional clearance for lug landing and arc-chamber venting per UL 489 / IEC 60947-2 installation rules.