Skip to main content
Siemens 3VA2125-7JP46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2125-7JP46-0AA0 SENTRON MCCB, 25A, 4-Pole, 330kA

MPN3VA2125-7JP46-0AA0
Active

Siemens SENTRON 3VA2125-7JP46-0AA0, molded case circuit breaker, 4-pole, 25 A, ETU550 electronic trip unit, breaking capacity 330 kA at 240 V, 242 kA at 415 V, current lifecycle stage.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2125-7JP46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2125-7JP46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.8 kA
Power loss, max.0.6 W

Protection & Trip Unit

3VA2125-7JP46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550

Construction & Connection

3VA2125-7JP46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2125-7JP46-0AA0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2125-7JP46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2125-7JP46-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

The Siemens SENTRON 3VA2125-7JP46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for a continuous current of 25 A across the full ambient temperature range from 40 °C to 70 °C, with no derating needed. It is fitted with an ETU550 electronic trip unit, which provides adjustable time-current protection curves—a key feature for coordinating with downstream devices in a selective coordination study. The breaker carries a breaking capacity of 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.8 kA at 690 V, making it suitable for high-fault-current installations such as main service entrance or large distribution switchboards.

Trip unit and protection settings

The ETU550 electronic trip unit supports adjustable long-time pickup (Ir), long-time delay (tr adjustable from 0.5 to 25 seconds), short-time pickup and delay, instantaneous pickup, and ground-fault protection (when the neutral protection is configured). The N-conductor protection is adjustable: OFF, 40%, up to 160% of the phase rating. This programmability allows the breaker to be fine-tuned for cable protection, motor branch circuits, or generator feeders without swapping trip units.

Physical integration

The breaker measures 140 mm wide, 181 mm high, and 86 mm deep. It mounts on a DIN rail or can be screw-fixed to a mounting plate in a standard enclosure. The IP40 protection rating on the front means it is protected against solid objects larger than 1 mm—adequate for indoor panel environments, but not for washdown or outdoor exposure without an additional enclosure. The 4-pole construction (3 phases + neutral) is typical for three-phase four-wire systems where the neutral must be switched and protected.

Communication capability

A communication function is present on this variant, enabling integration with higher-level control or energy management systems. This allows remote reading of trip events, load current, and status, which supports the audit trail for a GMP-regulated environment where undocumented changes are unacceptable. The specific protocol (e.g., PROFIBUS, PROFINET, Modbus) is not defined in the base listing and should be confirmed from the full order code extension or the communication module fitted.

Frequently asked questions

How do I get current pricing and availability for 3VA2125-7JP46-0AA0?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; pricing and lead time are confirmed at quote time and are not published here.

What is the breaking capacity of this MCCB at 415 V?

At 415 V the breaking capacity is 242 kA. At 240 V it is 330 kA, and at 690 V it drops to 3.8 kA.

What compliance documentation does Siemens provide for this part?

The SENTRON series typically carries IEC 60947-2 certification, CE marking, and RoHS/REACH compliance declarations. The specific approvals (UL, CSA, CCC) depend on the exact order code variant and should be verified from the nameplate or manufacturer documentation.

Will 3VA2125-7JP46-0AA0 drop into a panel specified around 5SQ2670-2YA63 without rewiring?

No. The 5SQ2670 series breakers have different dimensions, mounting patterns, and terminal arrangements than the 3VA2 SENTRON platform. A panel designed for the 5SQ2670-2YA63 will require mechanical modifications and potentially busbar rework to accept this breaker.

What is the rated continuous current at elevated ambient temperature?

The breaker is rated 25 A continuously from 40 °C through 70 °C with no derating—the full temperature-compensated rating holds across the operating range.

MPN
3VA2125-7JP46-0AA0