Skip to main content
Siemens 3VA2125-8HL46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2125-8HL46-0AA0 SENTRON MCCB, 4-pole, 25 A, 440 k

MPN3VA2125-8HL46-0AA0
Active

Siemens SENTRON 3VA2125-8HL46-0AA0, molded case circuit breaker, 4-pole, 25 A, 440 kA at 240 V, ETU320, IP40.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2125-8HL46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2125-8HL46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V53 kA
Power loss, max.0.5 W

Protection & Trip Unit

3VA2125-8HL46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320

Construction & Connection

3VA2125-8HL46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2125-8HL46-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2125-8HL46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2125-8HL46-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

The Siemens SENTRON 3VA2125-8HL46-0AA0 is a 4-pole molded case circuit breaker rated for 25 A continuous current across the full ambient range of 40 °C to 70 °C — no derating needed up to that ceiling. It carries an ETU320 electronic trip unit with adjustable N-conductor protection (OFF or 100%).

Breaking capacity is the headline: 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, 53 kA at 690 V. These are the maximum fault currents the breaker can safely interrupt at each voltage — critical for high-fault panels near large transformers or generators. The 4-pole version handles three-phase plus neutral, with the neutral pole configurable for no protection or full protection.

Mounts in a standard panel or enclosure — dimensions are 181 mm high, 140 mm wide, 86 mm deep. Front IP40 protection means it's suited for dry indoor panels; no washdown rating. The ETU320 trip unit is field-adjustable for long-time delay (tr min 0.5 s to tr max 17 s) and other parameters, so it can be tuned to coordinate with downstream breakers without swapping the unit.

Frequently asked questions

What is 3VA2125-8HL46-0AA0's listed depth (86 mm) on this component line?

The depth is 86 mm (3.4 in).

What is 3VA2125-8HL46-0AA0's listed width (140 mm) on this component line?

The width is 140 mm (5.5 in).

MPN
3VA2125-8HL46-0AA0