The interrupting capacity hits 440 kA at 240 V and 330 kA at 415 V and 440 V, dropping to 220 kA at 500 V and 52.5 kA at 690 V. That kind of headroom means it clears high-fault scenarios without cascading upstream — selectivity stays intact even on a stiff utility feed. Front-side IP40 keeps dust out of the mechanism in a clean panel environment; the enclosure is sized at 105 mm wide, 86 mm deep, 181 mm tall — standard 3-pole MCCB footprint for DIN-rail or screw-mount integration.
Integration and mounting notes
Mounts on DIN rail or via the screw-mount lugs that come with the frame. The front IP40 rating means it can go in a ventilated enclosure without a separate cover over the breaker face. Optional motor drive is available for remote tripping or re-closing schemes.