Skip to main content
Siemens 3VA2125-8HN32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2125-8HN32-0AA0 SENTRON MCCB, 25 A, 3-Pole, ETU35

MPN3VA2125-8HN32-0AA0
Active

Siemens SENTRON 3VA2125-8HN32-0AA0, molded case circuit breaker, 3-pole, 25 A, ETU350 electronic trip, 330 kA at 415 V, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2125-8HN32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2125-8HN32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.0.5 W

Protection & Trip Unit

3VA2125-8HN32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2125-8HN32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2125-8HN32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2125-8HN32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2125-8HN32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Molded case circuit breaker for line protection

The Siemens SENTRON 3VA2125-8HN32-0AA0 is a 3-pole molded case circuit breaker (MCCB) designed for line protection — meaning it sits upstream protecting a feeder or distribution bus, not a specific motor or load. Rated 25 A continuous at 40 °C, it holds that current all the way up to 70 °C without derating, which is useful in a packed panel where ambient heat builds. The ETU350 electronic trip unit gives you adjustable overload and short-circuit protection curves, so you can coordinate selectively with downstream breakers instead of relying on a fixed thermal-magnetic curve.

Interrupting capacity that covers most industrial services

At 415 V — common across European and much of Asian industrial supply — this MCCB interrupts 330 kA. That's enough for high-fault locations like a main switchboard near a large transformer. Even at 690 V it still handles 52.5 kA, so it's not limited to low-voltage distribution only. The 800 V rated insulation voltage confirms the internal clearances are sized for 690 V systems without derating the insulation.

Panel fit and environmental sealing

The 3VA2125-8HN32-0AA0 measures 105 mm wide by 181 mm tall by 86 mm deep. IP40 on the front.

MPN
3VA2125-8HN32-0AA0