Siemens 3VA2125-8KQ46-0AA0 — Molded Case Circuit Breakers (MCCB)

3VA2125-8KQ46-0AA0 SENTRON MCCB, 4-pole, 25 A, ETU860, 440 k

MPN3VA2125-8KQ46-0AA0
Active

SENTRON 3VA2125-8KQ46-0AA0, 4-pole molded case circuit breaker, 25 A rated continuous current, ETU860 electronic trip unit, 440 kA breaking capacity at 240 V, 86 x 140 x 181 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2125-8KQ46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2125-8KQ46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V53 kA
Power loss, max.0.5 W

Protection & Trip Unit

3VA2125-8KQ46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860

Construction & Connection

3VA2125-8KQ46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2125-8KQ46-0AA0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2125-8KQ46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2125-8KQ46-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

What it is and what the ratings mean for fit

The SENTRON 3VA2125-8KQ46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 25 A that holds flat across the full 40 °C to 70 °C operating range — no derating needed as the panel warms up, which is unusual for a compact-frame MCCB. The ETU860 electronic trip unit gives you adjustable long-time delay (tr) from 0.5 s to 25 s and N-conductor protection configurable OFF or 40 % to 160 % of the phase setting, so it handles both 3-phase and 3-phase + N distribution without a separate neutral breaker. Breaking capacity is the headline figure here: 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 53 kA at 690 V. Those numbers mean this breaker can interrupt fault currents up to those levels without welding its contacts or venting plasma into the panel — critical for high-fault installations like transformer secondaries or large motor control centers where upstream coordination demands a high-interrupting device. The 800 V rated insulation voltage (Ui) confirms it's rated for 690 V line-to-line systems with margin. Dimensions are 86 mm deep, 140 mm wide, 181 mm tall — a standard 4-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures. The IP40 front protection means it's splash-resistant from the front but not sealed; install it in a clean indoor panel, not a washdown zone.

Sourcing and lifecycle reality

The built-in communication function means it can integrate with higher-level monitoring systems via the SENTRON communication modules — useful for energy management or remote trip indication in a BMS or SCADA environment.

How it compares to the closest peer

The 3VA2163-8JQ32-0AA0 is the nearest functional sibling — same 4-pole frame, same ETU860 trip unit family, but rated for a higher continuous current. The deciding factor between them is the load current: the 3VA2125-8KQ46-0AA0 tops out at 25 A, while the 3VA2163-8JQ32-0AA0 carries a higher rating. If your BOM specifies 25 A, this is the correct order code; the sibling won't drop in without rewiring the load side.

Deployment context

Mounts on a DIN rail or direct-panel in a standard distribution board or motor control center. The 4-pole configuration with adjustable N-conductor protection makes it a natural fit for TN-S or TN-C-S systems where the neutral must be switched and monitored. Ground-fault monitoring via summation current formation (L + N) is built into the ETU860 — no external GFCI module needed for residual current detection.

Frequently asked questions

What is the breaking capacity of this MCCB at different voltages?

440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 53 kA at 690 V. These are the maximum fault currents it can safely interrupt at each voltage level.

What trip unit does the 3VA2125-8KQ46-0AA0 use?

It uses the ETU860 electronic trip unit with adjustable long-time delay (tr) from 0.5 s to 25 s and configurable N-conductor protection (OFF, 40 %, 60 %, 80 %, 100 %, 160 %).

Where can I buy the 3VA2125-8KQ46-0AA0 and how is it quoted?

It is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.