Skip to main content
Siemens 3VA2140-0HL36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-0HL36-0AA0 SENTRON MCCB, 40 A, 440 kA at 415

MPN3VA2140-0HL36-0AA0
Active

Siemens SENTRON 3VA2140-0HL36-0AA0, molded case circuit breaker, 3-pole, 40 A, 440 kA at 415 V AC, ETU320 LI electronic trip unit, line protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2140-0HL36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2140-0HL36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.1.2 W
3VA2140-0HL36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA2140-0HL36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2140-0HL36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2140-0HL36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2140-0HL36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

That's unusual for an MCCB; most thermal-magnetic units start dropping at 50 °C. The ETU320 electronic trip keeps the threshold stable across the panel's internal temperature rise. At 690 V it still clears 187 kA, which covers most 480/600 V industrial services in North America and 690 V European distribution.

Panel integration

Front IP40 protects against solid objects larger than 1 mm; the interior of the panel needs to be kept clean of dust and moisture. Optional motor drive for remote operation is supported.

Frequently asked questions

What is the breaking capacity of this MCCB?

440 kA at 415 V AC and 187 kA at 690 V AC. That's the ultimate short-circuit breaking capacity (Icu) — it can clear a fault at that level and still be reused.

Where can I buy 3VA2140-0HL36-0AA0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What trip unit does this breaker use?

The ETU320 electronic trip unit with LI protection (long-time and instantaneous). It's designed for line protection — cable and busbar, not motor overload.

MPN
3VA2140-0HL36-0AA0