Skip to main content
Siemens 3VA2140-5HL32-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-5HL32-0AB0 SENTRON MCCB, 40 A, 3-Pole, 187 k

MPN3VA2140-5HL32-0AB0

Siemens SENTRON 3VA2140-5HL32-0AB0, molded case circuit breaker, 3-pole, 40 A, ETU320 electronic trip unit, 187 kA breaking capacity at 240 VAC, 86 mm depth, 105 mm width.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2140-5HL32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21405HL320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA11
3VA2140-5HL32-0AB0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.1.6 W
3VA2140-5HL32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2140-5HL32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2140-5HL32-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2140-5HL32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2140-5HL32-0AB0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2140-5HL32-0AB0 is a 3-pole molded case circuit breaker (MCCB) rated for 40 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to that ceiling. It carries a 187 kA interrupting capacity at 240 VAC and 121 kA at 415/440 VAC, which puts it in the high-fault category for industrial distribution panels and motor control centers where available fault current is significant.

The 187 kA at 240 VAC and 121 kA at 415 VAC are the ultimate short-circuit breaking capacities (Icu) per IEC 60947-2. At 500 VAC it still clears 75.6 kA, and at 690 VAC the rating drops to 3.7 kA — a steep fall that reflects the arc-extinction challenge at higher voltages. For a 480 VAC panel (common in North America), the 75.6 kA at 500 VAC is the closest reference; for 400 VAC systems (Europe/Asia), the 121 kA at 415 VAC applies.

Trip unit and auxiliary configuration

The ETU320 electronic trip unit is the overcurrent release on this variant. It supports LSI protection (long-time, short-time, instantaneous) with adjustable pickups and time delays, which is what you need for selective coordination downstream of a transformer or upstream of feeder breakers. The basic switch order code is 3VA21405HL320AA0, which is the internal switching mechanism; the full breaker includes it.

The breaker is designed for screw-mounting to a backplate or mounting plate, not DIN rail.

Frequently asked questions

Where can I buy 3VA2140-5HL32-0AB0 and get a price?

This part is sourced through independent distribution and quoted to order against an RFQ. Submit a request for current availability and pricing — confirmed at quote time.

What is the breaking capacity of 3VA2140-5HL32-0AB0 at 240 V?

The ultimate short-circuit breaking capacity (Icu) at 240 VAC is 187 kA. At 415 VAC it is 121 kA, at 500 VAC it is 75.6 kA, and at 690 VAC it is 3.7 kA.

What trip unit does 3VA2140-5HL32-0AB0 use?

It uses the ETU320 electronic trip unit with LSI protection (long-time, short-time, instantaneous), adjustable pickups and time delays.

MPN
3VA2140-5HL32-0AB0