It carries an interrupting capacity of 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — meaning it can safely clear a fault up to those levels without welding its contacts or cascading the arc upstream.
Sizing and thermal performance
Maximum power loss is 1.6 W, so it won't cook adjacent devices in a dense DIN-rail layout.
Communication function is built in (ETU550 supports PROFIBUS or PROFINET communication modules for remote monitoring and trip-data readout).