Specifications

3VA2140-5MN36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2140-5MN36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classE
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.1.6 W
3VA2140-5MN36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2140-5MN36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2140-5MN36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2140-5MN36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2140-5MN36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Motor protection MCCB with high interrupting capacity

The Siemens 3VA2140-5MN36-0AA0 is a SENTRON molded case circuit breaker (MCCB) designed specifically for motor protection, rated 40 A continuous at 40 °C and carrying a 187 kA interrupting capacity at 240 V. That interrupting rating drops to 121 kA at 415 V and 75.6 kA at 500 V, so it handles high-fault-current industrial distribution panels where the available short-circuit current is substantial. The 3-pole construction with phase failure detection built in means it will trip on a lost phase before the motor single-phases and burns out — a common failure mode in older plant feeders. The adjustable trip class (10A, 10E, 20E) lets you match the thermal curve to the motor start profile: 10A for short acceleration times like pumps, 20E for high-inertia loads like centrifuges or large fans.

Frequently asked questions

What is the interrupting capacity of this MCCB at 240 V?

The interrupting capacity is 187 kA at 240 V, dropping to 121 kA at 415 V and 75.6 kA at 500 V. At 690 V it is rated 3.7 kA.

What trip classes are adjustable on this breaker?

The adjustable trip classes are 10A, 10E, and 20E, letting you tune the thermal overload curve to match motor starting characteristics.

Where can I buy 3VA2140-5MN36-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN