Skip to main content
Siemens 3VA2140-6HK46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-6HK46-0AA0 SENTRON MCCB, 40A, 4-Pole, 242kA

MPN3VA2140-6HK46-0AA0
Active

Siemens SENTRON 3VA2 series, Molded case circuit breaker, 3VA2140-6HK46-0AA0, 40 A, 4-pole, 242 kA at 240 V, ETU340 electronic trip unit, line protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2140-6HK46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2140-6HK46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V42 kA
Power loss, max.1.6 W
3VA2140-6HK46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340
3VA2140-6HK46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2140-6HK46-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2140-6HK46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2140-6HK46-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

The Siemens 3VA2140-6HK46-0AA0 is a SENTRON 3VA2 molded case circuit breaker (MCCB) rated for 40 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to the enclosure's thermal limit. Breaking capacity is the headline here: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 42 kA at 690 V. That SCCR headroom means this 4-pole breaker can be specified into panels fed from large transformers or high-capacity gensets without worrying about cascading failure upstream.

The IP40 front protection means it's suitable for enclosed switchboards where the door provides the environmental seal. At 1.6 W maximum power loss, heat dissipation inside the enclosure is manageable even in densely packed MCC sections.

Protection and configuration

The ETU340 release is a microprocessor-based trip unit with LSI protection curves (long-time, short-time, instantaneous) plus ground-fault capability — though this specific variant ships without ground-fault monitoring. Communication function is not fitted, so this is a standalone breaker for hardwired protection schemes.

Frequently asked questions

Where can I buy 3VA2140-6HK46-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings for 3VA2140-6HK46-0AA0?

Rated continuous current 40 A, 4 poles, breaking capacity 242 kA at 240 V and 187 kA at 415 V, ETU340 electronic trip unit, rated insulation voltage 800 V.

What does the ETU340 trip unit mean for protection?

The ETU340 is a microprocessor-based release offering adjustable long-time, short-time, and instantaneous protection (LSI curves), plus ground-fault capability — though this variant ships without ground-fault monitoring fitted.

MPN
3VA2140-6HK46-0AA0