Siemens 3VA2140-6HN36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-6HN36-0AA0 SENTRON MCCB, 40 A, 242 kA

MPN3VA2140-6HN36-0AA0
Active

Siemens SENTRON 3VA2 molded case circuit breaker, 3-pole, 40 A, line protection, ETU350 release, 242 kA at 240 V, 86 x 105 x 181 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2140-6HN36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2140-6HN36-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.1.6 W
3VA2140-6HN36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
3VA2140-6HN36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2140-6HN36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2140-6HN36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2140-6HN36-0AA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

MCCB for high-fault panels — 40 A, 242 kA

The interrupting capacity hits 242 kA at 240 V and 187 kA at 415 V and 440 V, dropping to 121 kA at 500 V and 3.7 kA at 690 V — this is a high-fault-rated MCCB sized for transformer secondaries, large motor control centers, or main feeders where available fault current is well above standard 25/36 kA breakers.

Current rating holds flat to 70 °C — no derate needed

Mounts on standard DIN rail. Dimensions are 105 mm wide (4.13 in), 181 mm tall (7.13 in), 86 mm deep (3.39 in) — that 86 mm depth includes the handle and terminals, so check gland-plate clearance on shallow enclosures. IP40 on the front face; the body is open to the panel interior for heat dissipation.

Frequently asked questions

Where can I buy 3VA2140-6HN36-0AA0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 3VA2140-6HN36-0AA0 drop into a panel built around 3VA2163-8HM32-0AA0 without rewiring?

Both are 3-pole SENTRON 3VA2 MCCBs on the same DIN-rail footprint, so the mechanical fit and bus-bar spacing are identical. The difference is the trip unit and rating — 3VA2163-8HM32-0AA0 is a higher-current variant with a different electronic release. Verify the load current and trip curve before swapping.

What compliance documentation does Siemens provide for 3VA2140-6HN36-0AA0?

Standard SENTRON MCCB documentation includes RoHS and REACH declarations, plus IEC 60947-2 and UL 489 certifications. Specific certificates are available on request.

MPN