Siemens 3VA2140-7HN32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-7HN32-0AA0 SENTRON MCCB, 40 A, 3-Pole, ETU35

MPN3VA2140-7HN32-0AA0
Active

Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2140-7HN32-0AA0, 40 A, 3-pole, ETU350 electronic trip unit, line protection design, 330 kA interrupting at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2140-7HN32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2140-7HN32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.1.6 W

Protection & Trip Unit

3VA2140-7HN32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2140-7HN32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2140-7HN32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2140-7HN32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2140-7HN32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

SENTRON 3VA2 MCCB, 40 A Frame

The Siemens 3VA2140-7HN32-0AA0 is a SENTRON 3VA2 molded case circuit breaker with a 40 A continuous current rating and a 3-pole configuration. It uses the ETU350 electronic trip unit, designed for line protection — meaning it handles overload and short-circuit protection in distribution panels, not motor or generator circuits. The interrupting capacity hits 330 kA at 240 V AC, so it safely clears high-fault-current faults common in large industrial services or transformer secondaries without cascading upstream. Rated insulation voltage is 800 V, and maximum power loss is 1.6 W. The breaker is rated for continuous full current from 40 °C through 70 °C ambient — no derating needed across that span, which simplifies panel layout in warm enclosures. It carries an IP40 protection rating on the front, meaning it's protected against tools and small solid objects but not moisture; keep it inside a panel or enclosure with a higher overall IP rating.

Dimensions and Panel Fit

The 3VA2140-7HN32-0AA0 measures 86 mm deep, 105 mm wide, and 181 mm high. That's a compact 3-pole MCCB footprint — it fits standard Siemens 3VA2 panel cutouts and busbar connections. No undervoltage release, no ground-fault monitoring, no communication function on this variant: it's a straight thermal-magnetic replacement with electronic trip, not a metering or remote-trip device.

Frequently asked questions

What is the interrupting capacity of 3VA2140-7HN32-0AA0 at different voltages?

The interrupting capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V.

Where can I buy 3VA2140-7HN32-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability.

MPN
3VA2140-7HN32-0AA0