Specifications

3VA2140-8HK32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2140-8HK32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.1.2 W
3VA2140-8HK32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340
Overcurrent protection functionELISA LI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2140-8HK32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2140-8HK32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2140-8HK32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2140-8HK32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB is and what it does

The Siemens 3VA2140-8HK32-0AA0 is a SENTRON molded case circuit breaker (MCCB) designed for line protection — meaning it sits at the feeder or distribution point to protect cables and downstream equipment from overloads and short circuits. It's a 3-pole unit rated for 40 A continuous current across the full ambient range from -25 °C to 70 °C, so no derating headache in a warm enclosure. The ETU340 electronic trip unit gives you adjustable overload and short-circuit protection curves, not a fixed thermal-magnetic element — useful for coordinating with downstream breakers on a selective scheme.

Breaking capacity — what the numbers mean for your fault level

This breaker carries a rated ultimate short-circuit breaking capacity (Icu) of 440 kA at 240 V AC, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V. Those are very high numbers — this is a current-limiting MCCB intended for high-fault installations where the available fault current is substantial. At 690 V the 52.5 kA still covers most industrial distribution panels. The insulation voltage is rated 800 V, so it's suitable for 480/277 V and 600/347 V systems without issue.

Panel fit and integration

Dimensions are 105 mm wide, 181 mm high, 86 mm deep — a standard 3-pole MCCB footprint that drops into most SENTRON panelboards and switchgear. The front face carries IP40 protection, so it's fine in a clean indoor enclosure; no washdown rating. Rated power loss is only 1.2 W maximum, which keeps enclosure heating negligible. No undervoltage release, no communication function, no ground-fault monitoring on this variant — it's a straight line-protection breaker with the ETU340 trip unit.

Frequently asked questions

Where can I buy 3VA2140-8HK32-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2140-8HK32-0AA0?

Rated Icu is 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V.

What trip unit does this MCCB use?

It uses the ETU340 electronic trip unit, which provides adjustable overload and short-circuit protection curves.

Will 3VA2140-8HK32-0AA0 fit in a panel designed for 3VA2040-8HN42-0AA0?

Both are SENTRON 3-pole 40 A MCCBs with the same frame size and mounting footprint (105 mm wide, 181 mm high, 86 mm deep), so a direct mechanical swap is possible. The key difference is the trip unit — this one uses ETU340 electronic, the other uses a different ETU variant — so verify the protection settings match your coordination study.

MPN