Skip to main content
Siemens 3VA2140-8HK46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-8HK46-0AA0 SENTRON MCCB, 40 A, 4-Pole, 440 k

MPN3VA2140-8HK46-0AA0
Active

Siemens SENTRON 3VA2140-8HK46-0AA0, Molded case circuit breaker, Line protection, 4-pole, 40 A, ETU340, 440 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2140-8HK46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2140-8HK46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V53 kA
Power loss, max.1.2 W

Protection & Trip Unit

3VA2140-8HK46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340

Construction & Connection

3VA2140-8HK46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2140-8HK46-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2140-8HK46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2140-8HK46-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

SENTRON 3VA2140-8HK46-0AA0 — 40 A MCCB with ETU340, 4-Pole

The Siemens SENTRON 3VA2140-8HK46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 40 A flat across the full operating temperature range from -40 °C to 70 °C — no derating needed up to the maximum. The ETU340 electronic trip unit provides adjustable N-conductor protection (OFF or 100%) and a fixed long-time delay tr of 1300 ms. Breaking capacity reaches 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 53 kA at 690 V, giving substantial SCCR headroom for most industrial distribution panels. Rated insulation voltage Ui is 800 V. Front-face protection is IP40.

Panel Fit and Integration

Footprint is 140 mm wide × 181 mm high × 86 mm deep — a standard SENTRON 3VA frame size that fits existing 4-pole MCCB cutouts and DIN-rail or screw-mount panel layouts. Maximum power loss is 1.2 W, so ventilation requirements are minimal even in dense enclosures. Latching endurance is rated at 20 000 cycles. Storage range spans -40 °C to 80 °C.

Frequently asked questions

Who supplies 3VA2140-8HK46-0AA0 and how is it quoted for volume purchases?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for volume pricing.

What is 3VA2140-8HK46-0AA0's listed depth?

The listed depth is 86 mm (3.4 in).

What is 3VA2140-8HK46-0AA0's listed width?

The listed width is 140 mm (5.5 in).

What breaking capacity does 3VA2140-8HK46-0AA0 offer at 415 V?

At 415 V the breaking capacity is 330 kA.

MPN
3VA2140-8HK46-0AA0