Skip to main content
Siemens 3VA2140-8HL32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-8HL32-0AA0 SENTRON MCCB, 40 A, 3-Pole, ETU32

MPN3VA2140-8HL32-0AA0
Active

Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2140-8HL32-0AA0, 40 A, 3-pole, ETU320 electronic trip unit, line protection, 440 kA interrupting at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2140-8HL32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2140-8HL32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.1.2 W

Protection & Trip Unit

3VA2140-8HL32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2140-8HL32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2140-8HL32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2140-8HL32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2140-8HL32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens 3VA2140-8HL32-0AA0 — SENTRON MCCB, 40 A, 3-Pole, ETU320

The Siemens 3VA2140-8HL32-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated for 40 A continuous current on a 3-pole configuration, fitted with an ETU320 electronic trip unit. It's designed for line protection — the primary role is guarding feeder circuits and downstream distribution against overloads and short circuits in a panel. The ETU320 trip unit gives you adjustable thermal-magnetic or electronic protection curves, which is the deciding factor for coordination studies — you can dial in the long-time pickup and short-time delay to achieve selectivity with downstream breakers. That 40 A rating holds flat across the full -25 °C to 70 °C operating range, so no derating headache in a warm enclosure. Interrupting capacity is substantial: 440 kA at 240 V, 330 kA at 415 V, and still 52.5 kA at 690 V. That high fault current handling means this MCCB can be installed close to the transformer secondary where available fault current is highest, without needing a current-limiting fuse upstream. Rated insulation voltage is 800 V, so it's suitable for 480/277 V and 600 V systems with margin. The IP40 front protection keeps dust out of the breaker mechanism in a typical enclosed panel — not rated for washdown, so keep it behind the panel door.

Integration & Mounting

Dimensions are 105 mm wide, 181 mm tall, 86 mm deep — fits standard Siemens 3VA2 panel cutouts and busbar connections. The 3-pole form factor is a direct swap for existing SENTRON 3VA2 breakers in the same frame size. No undervoltage release, no voltage trigger, no communication module on this variant — it's a straight line-protection breaker. Power loss is only 1.2 W maximum, so thermal buildup in a dense panel is negligible. Storage range from -40 °C to 80 °C covers most warehouse and shipping conditions.

Frequently asked questions

What is the interrupting capacity of this MCCB at 240 V?

440 kA at 240 V, with 330 kA at 415 V and 52.5 kA at 690 V.

What trip unit does the 3VA2140-8HL32-0AA0 use?

It uses an ETU320 electronic trip unit, which provides adjustable protection curves for coordination.

Where can I buy 3VA2140-8HL32-0AA0 and how is it quoted?

It's sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

Does this breaker have an undervoltage release or communication function?

No — this variant has no undervoltage release, no voltage trigger, and no communication module.

MPN
3VA2140-8HL32-0AA0