Skip to main content
Siemens 3VA2140-8KP32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-8KP32-0AA0 SENTRON MCCB, 40 A, 3-Pole, 440 k

MPN3VA2140-8KP32-0AA0
Active

Siemens SENTRON 3VA2140-8KP32-0AA0, molded case circuit breaker, 3-pole, 40 A, 440 kA at 240 V, ETU850 electronic release, IP40 front, 86 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2140-8KP32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2140-8KP32-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V53 kA
Power loss, max.1.2 W
3VA2140-8KP32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
3VA2140-8KP32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2140-8KP32-0AA0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0
3VA2140-8KP32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2140-8KP32-0AA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.1 in
Width (in)4.1 in
Depth (in)3.4 in

Product details

The 3-pole design with 800 V rated insulation voltage suits it for 400 V class distribution panels feeding motor control centers or branch circuits. Breaking capacity is the standout: 440 kA at 240 V AC, 330 kA at 415 V and 440 V, 220 kA at 500 V, and still 53 kA at 690 V. That means it handles high-fault scenarios upstream near the transformer or in industrial mains without cascading to downstream gear. For a panel builder, this avoids needing a current-limiting upstream breaker — the 3VA2140-8KP32-0AA0 clears the fault itself.

Communication and integration

This MCCB includes a communication function, which means it can report status and trip events to a higher-level control system — useful for a plant-wide power monitoring scheme. The ETU850 release offers adjustable time-current curves (tr min 0.5 s, tr max 25 s; tsd max 0.5 s) so you can coordinate selectivity with downstream breakers without sacrificing speed on hard faults.

Panel fit and mechanical endurance

Frequently asked questions

What is the breaking capacity of 3VA2140-8KP32-0AA0 at 415 V?

330 kA at 415 V AC, matching the rating at 440 V. At 240 V it reaches 440 kA, and at 690 V it still clears 53 kA.

What trip unit does 3VA2140-8KP32-0AA0 use?

It uses the ETU850 electronic release with adjustable time-current settings — tr from 0.5 s to 25 s, tsd up to 0.5 s.

Where can I buy 3VA2140-8KP32-0AA0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA2140-8KP32-0AA0