Siemens 3VA2163-0KQ36-0AA0 SENTRON MCCB, 63 A, 440 kA at 415

MPN3VA2163-0KQ36-0AA0
Active

Siemens SENTRON 3VA2163-0KQ36-0AA0, molded case circuit breaker, 3-pole, 63 A continuous, ETU860 electronic trip unit, 440 kA breaking capacity at 415 V, line protection design with communication function.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2163-0KQ36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2163-0KQ36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.3.1 W
3VA2163-0KQ36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes
3VA2163-0KQ36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-0KQ36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0
3VA2163-0KQ36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-0KQ36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens 3VA2163-0KQ36-0AA0 is a 3-pole SENTRON molded case circuit breaker rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling.

The 181 mm height clears most distribution board covers. Front IP40 protection means it's suited for enclosed panels where splash or tool ingress is minimal — not for washdown zones. The ETU860 trip unit's communication function requires a separate 24 V supply for the electronics; verify that your control transformer or power supply has the headroom.

Frequently asked questions

What is the breaking capacity of this MCCB at 415 V?

Rated 440 kA at 415 V, which covers most industrial transformer-secondary and large motor feeder fault levels without needing upstream current-limiting fuses.

Where can I buy 3VA2163-0KQ36-0AA0 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response.

What compliance documentation does Siemens provide for this part?

As a SENTRON MCCB, it carries IEC 60947-2 certification and is CE-marked for the European market. RoHS and REACH declarations are available from Siemens on request.

Will 3VA2163-0KQ36-0AA0 drop into a panel specified for 3VA2163-8HM32-0AA0?

Both are 3-pole 3VA2 frame breakers with the same 105 mm width and 86 mm depth, so the mechanical footprint is identical. The difference is in the trip unit and accessories — the -0KQ36-0AA0 carries an ETU860 with communication, while the -8HM32-0AA0 uses a different release variant. Verify the trip curve and auxiliary contact configuration before swapping.

MPN
3VA2163-0KQ36-0AA0