Skip to main content
Siemens 3VA2163-5HL32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5HL32-0AF0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA2163-5HL32-0AF0

Siemens SENTRON 3VA2163-5HL32-0AF0, molded case circuit breaker, 3-pole, 63 A, ETU320 electronic trip, 187 kA at 240 V, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2163-5HL32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2163-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2163-5HL32-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.4 W
3VA2163-5HL32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2163-5HL32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-5HL32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2163-5HL32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-5HL32-0AF0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

The Siemens SENTRON 3VA2163-5HL32-0AF0 is a 3-pole molded case circuit breaker rated for 63 A continuous current (Iu) at 40 °C, with an ETU320 electronic trip unit providing adjustable overload and short-circuit protection for line-feeder or main-switch applications. Its interrupting capacity reaches 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V — figures that cover most industrial fault-current scenarios without cascading upstream breakers.

Thermal derating and endurance

Above that, current must be derated: 60.6375 A at 55 °C, 58.275 A at 60 °C, 55.9125 A at 65 °C, and 53.55 A at 70 °C. Latching endurance is rated at 20 000 operations, and maximum power loss is 4 W.

Physical footprint and auxiliary contacts

Frequently asked questions

What is the interrupting capacity of 3VA2163-5HL32-0AF0 at 415 V?

121 kA at 415 V AC, matching the rating at 440 V. At 240 V it reaches 187 kA, at 500 V it is 79 kA, and at 690 V it is 4.25 kA.

Where can I buy 3VA2163-5HL32-0AF0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA2163-5HL32-0AF0