Skip to main content
Siemens 3VA2163-5HL32-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2163-5HL32-0AG0 MCCB, 63 A, 3-pole, 187 k

MPN3VA2163-5HL32-0AG0

Siemens SENTRON molded case circuit breaker, 3VA2163-5HL32-0AG0, 63 A, 3-pole, line protection, ETU320 release, breaking capacity 187 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2163-5HL32-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2163-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA2163-5HL32-0AG0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.4 W
3VA2163-5HL32-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2163-5HL32-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-5HL32-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2163-5HL32-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-5HL32-0AG0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

What matters for the BOM line is the breaking capacity: 187 kA at 240 V AC, 121 kA at 415/440 V, 79 kA at 500 V, and 4.25 kA at 690 V.

If you're swapping out an older 3VA1 or a competitor's 3-pole MCCB, check the mounting hole pattern; the 3VA2 series uses the same bolt spacing as the previous generation, so a drop-in replacement is likely without redrilling the backplate.

Environmental and endurance data

For a main feeder breaker that cycles a few times a year, that's effectively a lifetime. Maximum power loss is 4 W, which is negligible for panel thermal calculations.

This is a current-production part with no obsolescence signals. The manufacturer lists it as 'current' lifecycle stage. No minimum order quantity is implied by the lifecycle status. The official base variant is 3VA2163-5HL32-0AA0 (without the auxiliary switch option); the -0AG0 suffix adds the 1 auxiliary + 1 alarm switch configuration.

MPN