Skip to main content
Siemens 3VA2163-5HL32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5HL32-0BH0 SENTRON MCCB, 63 A, 3-Pole, ETU32

MPN3VA2163-5HL32-0BH0

Siemens SENTRON 3VA2163-5HL32-0BH0, molded case circuit breaker, 3-pole, 63 A, ETU320 electronic trip unit, line protection, with undervoltage release (UVR) and 2 aux + 1 trip alarm switch HQ.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2163-5HL32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2163-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2163-5HL32-0BH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.6.5 W
3VA2163-5HL32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2163-5HL32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-5HL32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2163-5HL32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-5HL32-0BH0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

SENTRON 3VA2163-5HL32-0BH0 — 63 A MCCB with ETU320 and Undervoltage Release

Breaking capacity is voltage-dependent: 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V. The 63 A rating holds from 40 °C through 50 °C, then derates linearly to 53.55 A at 70 °C — useful for panel builders working with elevated ambient temperatures inside enclosures.

The 3-pole form factor with screw terminals accepts standard busbar and cable connections. Power loss is 6.5 W maximum, which keeps thermal rise manageable in dense panels. Mechanical endurance is rated at 20,000 operations, and the operating temperature range spans -25 °C to 70 °C, with storage from -40 °C to 80 °C.

Trip Unit and Auxiliary Configuration

No communication function, phase failure detection, or ground fault monitoring is included on this variant — it is a pure line-protection device.

Frequently asked questions

Where can I buy 3VA2163-5HL32-0BH0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What are the key ratings for 3VA2163-5HL32-0BH0?

Rated continuous current Iu is 63 A, breaking capacity is 187 kA at 240 V and 121 kA at 415/440 V, with a 3-pole configuration and ETU320 electronic trip unit. Includes undervoltage release and 2 aux + 1 trip alarm switch.

What compliance documentation is available for this MCCB?

As a Siemens SENTRON product, it carries the standard certifications for the 3VA series including IEC/EN 60947-2, UL 489, and CSA C22.2 No. 5. RoHS and REACH declarations are available from Siemens documentation.

MPN