Siemens 3VA2163-5HL36-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5HL36-0AH0 SENTRON MCCB, 63 A, 3-Pole, 187 k

MPN3VA2163-5HL36-0AH0

Siemens SENTRON 3VA2163-5HL36-0AH0, molded case circuit breaker, 3-pole, 63 A continuous rating, 187 kA breaking capacity at 240 V AC, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-5HL36-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21635HL360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2163-5HL36-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W

Protection & Trip Unit

3VA2163-5HL36-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-5HL36-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-5HL36-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2163-5HL36-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-5HL36-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens SENTRON 3VA2163-5HL36-0AH0 — 63 A MCCB for Line Protection

The Siemens SENTRON 3VA2163-5HL36-0AH0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current at up to 70 °C ambient, meaning it holds its full rating across a wide panel temperature range without derating — useful when the breaker sits near other heat-generating components in a crowded enclosure. Its breaking capacity is 187 kA at 240 V AC, dropping to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 3.7 kA at 690 V — the high 187 kA figure at 240 V makes it suitable for installation close to large transformers or high-fault-capacity utility feeds where upstream fault current can exceed 100 kA. Rated insulation voltage is 800 V, and the breaker is designed specifically for line protection (not motor or generator protection), so it coordinates well with downstream branch breakers in a selective coordination study.

Integration — Dimensions, Auxiliaries, and Panel Fit

Dimensions are 181 mm height, 105 mm width, and 86 mm depth — a standard SENTRON 3VA2 frame size that mounts on a DIN rail or directly to a backplate in a distribution panel. The breaker ships with a pre-installed auxiliary switch block: 2 auxiliary switches plus 1 trip alarm switch (HQ type), which provides remote status indication for the open/closed and tripped states without needing a separate add-on module. The basic switch assembly carries order code 3VA21635HL360AA0, which is the replaceable switching mechanism inside the molded case — useful to know if the breaker trips frequently under fault and the contacts need swapping rather than replacing the whole unit. A mechanical trip indicator is present, and the breaker has no undervoltage release, no ground-fault monitoring, and no communication function — it is a straightforward thermal-magnetic line-protection device without extra electronics. Maximum power loss is 4 W, which is low enough that no forced cooling is needed in a standard IP40 enclosure, but the designer should still account for it in the thermal budget if multiple breakers are ganged.

Temperature Range and Storage

Operating ambient range is -25 °C to +70 °C; storage range is -40 °C to +80 °C. The 70 °C operating max matches the continuous current rating, so the breaker can be installed in a hot machine cabinet or near a furnace without derating.

Frequently asked questions

What are the physical dimensions of 3VA2163-5HL36-0AH0?

Height 181 mm, width 105 mm, depth 86 mm.

Does 3VA2163-5HL36-0AH0 include auxiliary switches?

Yes, it comes with 2 auxiliary switches plus 1 trip alarm switch (HQ type) pre-installed.

MPN
3VA2163-5HL36-0AH0