Skip to main content
Siemens 3VA2163-5HL36-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5HL36-0HC0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA2163-5HL36-0HC0

Siemens SENTRON 3VA2163-5HL36-0HC0, 3-pole molded case circuit breaker, 63 A rated continuous current at 40 °C, 187 kA breaking capacity at 240 V AC, ETU320 electronic trip unit, shunt trip (STL), 2 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-5HL36-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2163-5HL36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2163-5HL36-0HC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.4 W
3VA2163-5HL36-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2163-5HL36-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-5HL36-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2163-5HL36-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-5HL36-0HC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

63 A MCCB with 187 kA interrupting capacity

The Siemens 3VA2163-5HL36-0HC0 is a 3-pole SENTRON molded case circuit breaker rated for 63 A continuous current at 40 °C ambient, with a breaking capacity of 187 kA at 240 V AC. That interrupting rating drops to 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V — so the voltage class you're protecting determines which fault level this breaker can clear.

Above that it derates: 60.6375 A at 55 °C, 58.275 A at 60 °C, 55.9125 A at 65 °C, and 53.55 A at 70 °C. The 4 W maximum power loss matters for enclosure heat budgeting in a sealed panel.

Line protection configuration

The shunt trip (STL) allows a remote signal to trip the breaker, useful for emergency-stop circuits or supervisory shutdown. Two HQ auxiliary switches provide normally-open/normally-closed contacts for panel indication or PLC inputs.

Mechanical footprint and endurance

Frequently asked questions

Where can I buy 3VA2163-5HL36-0HC0?

This part is sourced and quoted to order against an RFQ through independent distribution channels; availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB at different voltages?

Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V.

What trip unit and accessories does 3VA2163-5HL36-0HC0 include?

It includes an ETU320 electronic trip unit, a built-in shunt trip (STL) for remote tripping, and two HQ auxiliary switches. No undervoltage release, ground-fault monitor, or communication module.

What are the physical dimensions of this breaker?

Width is 105 mm, height is 181 mm, depth is 86 mm.

MPN