That 63 A holds flat through 50 °C — only starts to derate above 55 °C, hitting 53.55 A at 70 °C. For a 63 A feeder in a warm enclosure, that thermal curve buys you margin. Breaking capacity is the headline number here: 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V.
Panel fit and footprint
The 86 mm depth includes the rotary handle and terminal covers; verify clearance against the enclosure door or gland plate if you're retrofitting into a tight panel.