Skip to main content
Siemens 3VA2163-5HL46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2163-5HL46-0AA0 MCCB, 63 A, 4-Pole, 187 k

MPN3VA2163-5HL46-0AA0
Active

Siemens SENTRON 3VA2163-5HL46-0AA0, molded case circuit breaker, 4-pole, 63 A rated continuous current, ETU320 electronic trip unit, breaking capacity 187 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-5HL46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2163-5HL46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W
3VA2163-5HL46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2163-5HL46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-5HL46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2163-5HL46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-5HL46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

It carries an adjustable thermal-magnetic or electronic trip range from a minimum of 95 A up to a maximum of 756 A, meaning the trip threshold can be field-set to match the protected conductor or load without swapping the breaker frame. Breaking capacity is rated at 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — the 240 V figure covers the highest fault-current scenario typical in North American 277/480 V panelboards, while the 415/440 V ratings handle European 400 V industrial mains.

Integration — Panel Fit and Mounting

Frequently asked questions

What trip unit does 3VA2163-5HL46-0AA0 use?

It uses the ETU320 electronic trip unit, which provides adjustable overload and short-circuit protection curves for selective coordination.

MPN