Its breaking capacity reaches 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — so the interrupting rating you rely on shifts with system voltage, and at 690 V the available fault current must be kept under 3.7 kA for this breaker to clear safely.
Maximum power loss is 4 W, a figure to include in enclosure thermal calculations.