Skip to main content
Siemens 3VA2163-5HN32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2163-5HN32-0CA0 MCCB, 63 A, 3-Pole, 187 k

MPN3VA2163-5HN32-0CA0

Siemens SENTRON 3VA2163-5HN32-0CA0, molded case circuit breaker, 3-pole, 63 A rated continuous current, 187 kA interrupting at 240 V, line protection design, includes undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-5HN32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21635HN320AA0

Ratings

3VA2163-5HN32-0CA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.6.5 W

Protection & Trip Unit

3VA2163-5HN32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-5HN32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-5HN32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2163-5HN32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-5HN32-0CA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB is and what it does

The Siemens SENTRON 3VA2163-5HN32-0CA0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current at 40 °C through 70 °C — no derating needed across that span, which simplifies panel layout when ambient runs warm. It carries 187 kA interrupting capacity at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V, so it handles high-fault service entrances and distribution feeders without cascading upstream. The design is line protection, not motor protection — no ground-fault monitoring, no communication module, no trip indicator. It ships with an undervoltage release (UVR) fitted, which drops the breaker if control voltage is lost, a common requirement for emergency-stop circuits and safety disconnects.

Where it fits in the panel

Mounts on a DIN rail or direct-panel screw fix. Dimensions are 181 mm high, 105 mm wide, 86 mm deep — standard SENTRON 3VA2 frame size, so it drops into existing 3VA cutouts without re-drilling. The UVR coil is factory-installed; no extra wiring for the release function. Rated insulation voltage is 800 V, covering 480/600 V distribution panels with margin.

Frequently asked questions

Where can I buy 3VA2163-5HN32-0CA0 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is 3VA2163-5HN32-0CA0's interrupting capacity at 240 V?

187 kA at 240 V. Also rated 121 kA at 415/440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V.

Does 3VA2163-5HN32-0CA0 include an undervoltage release?

Yes, it ships with an undervoltage release (UVR) fitted. The release design is an undervoltage release (UVR) type.

MPN
3VA2163-5HN32-0CA0