Skip to main content
Siemens 3VA2163-5HN36-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5HN36-0DA0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA2163-5HN36-0DA0

Siemens SENTRON 3VA2163-5HN36-0DA0, molded case circuit breaker, 3-pole, 63 A rated continuous current, ETU350 electronic trip unit, line protection version, with undervoltage release, 187 kA breaking capacity at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-5HN36-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2163-5HN36-0AA0
3VA2163-5HN36-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.6.5 W
3VA2163-5HN36-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2163-5HN36-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-5HN36-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2163-5HN36-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-5HN36-0DA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

What the ratings mean for fit

The Siemens 3VA2163-5HN36-0DA0 is a SENTRON molded case circuit breaker (MCCB) configured for line protection — meaning it protects cables and busbars against overload and short-circuit, not motor overload curves. The 63 A rated continuous current (Iu) holds at ambient temperatures up to 50 °C without derating; above that, the thermal curve steps down: 60.6 A at 55 °C, 58.3 A at 60 °C, 55.9 A at 65 °C, and 53.6 A at 70 °C. If your panel ambient runs above 50 °C, size the breaker for the derated value, not the nameplate 63 A. Breaking capacity is voltage-dependent and substantial: 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V. The 187 kA figure at 240 V means this breaker can interrupt a fault of that magnitude without rupturing — critical for high-available-fault-current installations like transformer secondaries or large busway feeds. At 690 V the capacity drops to 4.25 kA, which still covers most industrial 690 V distribution but not high-fault locations. The ETU350 electronic trip unit provides adjustable overload and short-circuit protection curves. This variant includes an undervoltage release (UVR) — the integrated auxiliary trip is order code 3VA9608-0BB25. The UVR trips the breaker when supply voltage drops below a set threshold, which is standard for safety disconnects on machine feeds or conveyor lines where loss of control voltage must open the main power path.

Panel integration and mounting

Dimensions: 105 mm wide, 181 mm high, 86 mm deep — a standard SENTRON 3VA2 frame size. The 105 mm width is three pole modules at 35 mm per pole, so it occupies three 18 mm DIN positions if panel-mounted via the optional base. Verify the mounting accessory (not included) matches your enclosure's busbar or backplate pattern. Power loss is 6.5 W maximum at rated current — negligible for thermal budgeting in a ventilated enclosure, but worth noting if the panel is sealed and densely packed with multiple breakers. The operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Frequently asked questions

What is the breaking capacity of this MCCB at different voltages?

187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V.

Does this breaker include an undervoltage release?

Yes, it is equipped with an undervoltage release (UVR). The integrated auxiliary trip is order code 3VA9608-0BB25.

Where can I buy 3VA2163-5HN36-0DA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the physical dimensions of this breaker?

Width 105 mm, height 181 mm, depth 86 mm.

What trip unit does this MCCB use?

The ETU350 electronic trip unit with adjustable overload and short-circuit protection.

MPN
3VA2163-5HN36-0DA0