It carries 187 kA breaking capacity at 240 V AC and 121 kA at 415/440 V AC — numbers that tell you it handles serious fault current without cascading upstream.
Ambient operating range is -25 °C to 70 °C, with no derating needed up to 50 °C at 63 A; above that, current tapers to 53.55 A at 70 °C.
Rated insulation voltage 800 V. Breaking capacity at 690 V: 4.25 kA. Maximum power loss 6.5 W. Mechanical endurance 20,000 operations.