Skip to main content
Siemens 3VA2163-5HN42-0AA0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA2163-5HN42-0AA0 MCCB, 63 A, 4-Pole, 187 kA at 240

MPN3VA2163-5HN42-0AA0
Active

SENTRON 3VA2163-5HN42-0AA0, molded case circuit breaker, 4-pole, 63 A, ETU350 electronic trip unit, line protection version, breaking capacity 187 kA at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-5HN42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2163-5HN42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W

Protection & Trip Unit

3VA2163-5HN42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout

Construction & Connection

3VA2163-5HN42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-5HN42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2163-5HN42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-5HN42-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

63 A MCCB with ETU350 — full-rated current across the ambient range

The SENTRON 3VA2163-5HN42-0AA0 is a 4-pole molded case circuit breaker rated for 63 A continuous current (Iu) with no derating needed from -25 °C up through 70 °C ambient — the full 63 A holds at every point in that operating range. That makes it a straightforward drop-in for a 63 A feeder or main breaker in a panel that sees elevated internal temperatures. Breaking capacity is 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. At the common 415 V distribution level, 121 kA covers high-fault installations like large transformer secondaries or industrial substations without needing a current-limiting upstream device. The ETU350 electronic trip unit provides adjustable overload and short-circuit protection with an LSI curve (long-time, short-time, instantaneous). The N-conductor protection is configurable — adjustable OFF or 100% of the phase current — which matters for 4-wire systems where the neutral may need full-rated protection or none.

Panel fit and integration

Dimensions are 181 mm height, 140 mm width, 86 mm depth — a standard MCCB footprint that fits most 4-pole breaker slots in SENTRON distribution boards and third-party enclosures. IP40 on the front face means it is protected against tools and small wires entering the breaker front; the rear terminals are open to the panel interior and rely on the enclosure's own IP rating. Rated insulation voltage Ui is 800 V, so the breaker is suitable for 690 V AC systems with adequate clearance. Power loss is 4 W maximum at rated current — negligible for thermal budgeting in a crowded panel. No undervoltage release, no shunt trip (voltage trigger), no communication module, and no ground-fault monitoring are fitted on this variant. If any of those are needed, the order code must be adjusted to a version that includes them.

Frequently asked questions

Does the 3VA2163-5HN42-0AA0 include a ground-fault module or communication?

No. This variant has no ground-fault monitoring, no communication function, no undervoltage release, and no shunt trip. It is a straight line-protection breaker with the ETU350 electronic trip unit.

What are the storage temperature limits for this breaker?

-40 °C minimum, 80 °C maximum during storage. Operating range is -25 °C to 70 °C.

MPN