Skip to main content
Siemens 3VA2163-5JP32-0AJ0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5JP32-0AJ0 SENTRON MCCB, 63 A, ETU550, 187 k

MPN3VA2163-5JP32-0AJ0

Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2163-5JP32-0AJ0, 63 A, 3-pole, ETU550 electronic trip unit, 187 kA at 240 V, line protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2163-5JP32-0AJ0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2163-5JP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA2163-5JP32-0AJ0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.4 W
3VA2163-5JP32-0AJ0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
3VA2163-5JP32-0AJ0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-5JP32-0AJ0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2163-5JP32-0AJ0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-5JP32-0AJ0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

SENTRON 3VA2 with ETU550 — 63 A line protection

Breaking capacity runs 187 kA at 240 V, 121 kA at 415/440 V, 79 kA at 500 V, and 4.25 kA at 690 V — so the same frame covers high-fault industrial mains and lower-fault distribution without a frame-size jump.

Rated 63 A straight through 50 °C; above that the ETU550 derates linearly — 60.6 A at 55 °C, 58.3 A at 60 °C, 55.9 A at 65 °C, 53.6 A at 70 °C. Footprint is 105 mm wide × 181 mm tall × 86 mm deep — standard 3-pole MCCB envelope for a 400 A frame. Front IP40, so it lives inside a closed enclosure, not exposed washdown.

Auxiliary contacts and communication

Communication function is onboard, so it can report status to a higher-level system without an add-on module.

Frequently asked questions

How do I get pricing and availability for 3VA2163-5JP32-0AJ0?

Submit an RFQ through this listing; the part is sourced to order through independent distribution, and current pricing and lead time are confirmed at quote time.

What are the key ratings for 3VA2163-5JP32-0AJ0?

63 A continuous current (Iu), 3-pole, ETU550 electronic trip unit, breaking capacity 187 kA at 240 V, 121 kA at 415/440 V, 79 kA at 500 V, 4.25 kA at 690 V. Dimensions 105 mm wide × 181 mm tall × 86 mm deep.

Will 3VA2163-5JP32-0AJ0 drop into a panel specified around 5SQ2370-2YA05?

The 3VA2 frame is a different mechanical platform from the 5SQ series — footprint and mounting hole patterns differ. A direct drop-in without rewiring or drilling new mounting points is not guaranteed; verify panel cutout dimensions against the 105 mm width and 86 mm depth before ordering.

MPN
3VA2163-5JP32-0AJ0