Skip to main content
Siemens 3VA2163-5JP32-0BL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5JP32-0BL0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA2163-5JP32-0BL0

Siemens SENTRON 3VA series molded case circuit breaker, 3VA2163-5JP32-0BL0, 3-pole, 63 A, 187 kA at 240 V, ETU550 electronic trip unit, undervoltage release, communication function.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2163-5JP32-0BL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2163-5JP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2163-5JP32-0BL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.6.5 W
3VA2163-5JP32-0BL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
3VA2163-5JP32-0BL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-5JP32-0BL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2163-5JP32-0BL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-5JP32-0BL0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

The Siemens 3VA2163-5JP32-0BL0 is a 3-pole SENTRON molded case circuit breaker rated for 63 A continuous current at 40 °C, with an interrupting capacity of 187 kA at 240 V AC — enough to handle high-fault utility feeds or transformer secondaries without cascading upstream. The communication function (likely PROFIBUS or PROFINET via a communication module) lets the breaker report status and trip events to a PLC or SCADA — useful for remote diagnostics on a production line.

Maximum power dissipation is 6.5 W.

Temperature derating and ambient limits

Above 50 °C it steps down: 60.6 A at 55 °C, 58.3 A at 60 °C, 55.9 A at 65 °C, and 53.6 A at 70 °C.

The interrupting capacity varies with system voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V. For a 480 V panel, you're looking at roughly 100 kA class — sufficient for most industrial service entrances and distribution boards.

Frequently asked questions

Does this breaker include an undervoltage release?

Yes, it comes with an integrated undervoltage release (UVR) that trips the breaker on loss of control voltage — useful for safety circuits and emergency-stop chains.

What trip unit does 3VA2163-5JP32-0BL0 use?

It uses the ETU550 electronic trip unit with adjustable long-time, short-time, and instantaneous protection curves, plus ground-fault alarm capability.

Will this breaker fit in a panel designed for 5SQ2370-2YA05?

The 3VA2163-5JP32-0BL0 uses a standard SENTRON 3VA3 frame (105 mm wide, 181 mm tall, 86 mm deep). The 5SQ2370 series breakers are a different platform — verify mounting hole patterns and bus-bar spacing before assuming a drop-in replacement. We can cross-reference dimensions on request.

MPN
3VA2163-5JP32-0BL0