Skip to main content
Siemens 3VA2163-5JP32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5JP32-0KC0 SENTRON MCCB, 63A, 3P, 187kA@240V

MPN3VA2163-5JP32-0KC0

Siemens SENTRON 3VA2163-5JP32-0KC0, molded case circuit breaker, 3-pole, 63 A continuous, 187 kA breaking capacity at 240 VAC, line protection design, with communication function and shunt trip release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2163-5JP32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21635JP320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2163-5JP32-0KC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W

Protection & Trip Unit

3VA2163-5JP32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2163-5JP32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2163-5JP32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2163-5JP32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2163-5JP32-0KC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

63 A MCCB with 187 kA interrupting capacity — line protection for high-fault panels

The Siemens SENTRON 3VA2163-5JP32-0KC0 is a 3-pole molded case circuit breaker rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Its interrupting capacity hits 187 kA at 240 VAC, 121 kA at 415/440 VAC, and still manages 75.6 kA at 500 VAC, making it a fit for high-fault industrial distribution where standard MCBs would weld shut. The 86 mm depth × 105 mm width × 181 mm height footprint matches the SENTRON 3VA frame, so it lands in the same panel cutout as other 3VA2 breakers.

Built-in communication and shunt trip — not a bare breaker

This variant ships with a communication function and a shunt trip release (STL) as the auxiliary release, plus two HQ auxiliary switches. That means it can report status and accept a remote trip signal without an add-on module — useful for emergency-off circuits or PLC-driven load shedding. The undervoltage release is absent by design, so the breaker holds in regardless of control power state; if you need UVR protection, this isn't the variant.

Current production — no obsolescence concern

Lifecycle status is current, so this order code is still in active manufacture from Siemens. No last-time-buy clock, no substitute hunt needed. For volume or project-pricing requests, the part is quoted to order against an RFQ through independent distribution.

Panel fit and thermal limits

Three-pole frame at 105 mm wide — standard 3VA2 panel cutout. Operating range from -25 °C to 70 °C ambient; storage from -40 °C to 80 °C. Maximum power loss is 4 W, negligible for enclosure heat load calculations. The 63 A rating holds flat across the entire ambient span, so no derating curve to apply in a warm cabinet.

Frequently asked questions

Where can I buy 3VA2163-5JP32-0KC0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 3VA2163-5JP32-0KC0 at different voltages?

At 240 VAC it interrupts 187 kA; at 415 VAC and 440 VAC, 121 kA; at 500 VAC, 75.6 kA; and at 690 VAC, 3.7 kA. The 187 kA rating at 240 V makes it suitable for high-fault-capacity panels where standard breakers would fail.

Will 3VA2163-5JP32-0KC0 drop into a panel specified around 3VA2163-8JQ32-0AA0?

Both are 3-pole 3VA2 frame breakers with the same 105 mm width and 86 mm depth, so they share the same panel cutout and bus connection pattern. The difference is in the auxiliary configuration and release type — this unit carries a shunt trip and communication function, while the 8JQ32 variant has different auxiliaries. Check the specific auxiliary wiring before swapping.

MPN
3VA2163-5JP32-0KC0